2
|
Troubleshooting
2.3.57 L1-00 – Outdoor unit: Main PCB abnormality
2.3.58 L3-00 – Outdoor unit: Electrical box temperature rise problem
Service manual
50
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the refrigerant pressure sensor. See
pressure
sensor" [
4
Possible cause: Faulty refrigerant pressure sensor.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Outdoor unit main PCB
detects current/voltage
errors.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check if the power supply is conform with the regulations. See
4
circuit" [
284].
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance >4%),
▪ Power drop,
▪ Short circuit.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Switch box temperature is
too high.
244].
"3.14 Main
Effect
Unit will stop operating.
"3.14 Main
Effect
Unit will stop operating.
"3.19 Refrigerant
4
PCB" [
171].
Reset
Manual reset via user
interface.
Power reset.
"4.1 Electrical
4
PCB" [
171].
Reset
Manual reset via remote
controller.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03