Table 17. Electrical Output (All Models)
Nominal Outputs
Frequency
Output Overload
(Normal Mode)
Output Overload
(Bypass Mode)
Output Overload
(Battery Mode)
Voltage Waveform
Harmonic
Distortion
Transfer Time
Power Factor
Load Crest Factor
High Voltage Models
200/208/220/230/240V
(voltage configurable or
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
50 or 60 Hz, autosensing
108%±5%–150%±5%: Load transfers to Fault mode after
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
100%±5%–130%±5%: Load transfers to Fault mode after
20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after
2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after
15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
108%±5%–150%±5%: Load transfers to Fault mode after
30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
<3% THD on linear load; <5% THD on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of
46
auto-sensing)
30 seconds.
Sine wave
utility)
0.9
3 to 1