To Install The Rail Kit; Securing The Rails; Fixing The Rails - KStar MEMO PLUS RT II (MP9100RTII-0.9) 1-3K User Manual

1kva to 3kva 0track-tower conversion
Table of Contents

Advertisement

To install the rail kit:

1. Assemble the left and right rails to the rear rails as shown in Figure3.Do not tighten the screws.
Adjust each rail size for the depth of your rack.
2. Select the proper size in the rack for positioning the UPS (see Figure 4). The rail occupies four
positions on the front and rear of the rack.
3. Tighten four M5 Umbrella Nuts in the side of rail assembly (see Figure 3).
4. Fix one rail assembly to the front of the rack with one M5×12 pan-head screw and one M5 cage
nut. Using two M5 cage nuts and two M5×12 pan-head screws, to fix the rail assembly to the rear
of the rack.
5. Repeat Steps 3 and 4 for the other rail assembly.
6. Tighten the four butterfly nuts in the middle of each rail assembly.
7. If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit.
8. Place the UPS on a flat, stable surface with the front of the cabinet facing to you.
Figure3 Securing the Rails
Figure4 Fixing the Rails
9