  • Page 2 All rights reserved. The information in this document is subject to change without notice. Publish statement Thank you for purchasing this series UPS. This series UPS is an intelligent, three phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, This UPS has become standard product which meets the world’s advanced level.
  • Page 3: Table Of Contents

    Contents 1.Safety................................2 1.1 Safety notes ............................2 1.2 Symbols used in this guide ......................2 2.Main Features ............................. 3 2.1 Summarization ........................... 3 2.2 Functions and Features ........................3 3.Installation ..............................4 3.1 Unpack checking ..........................4 3.2 UPS Module Outlook ........................4 3.3 PDU Module Outlook (Optional) ....................
  • Page 4: 1.Safety

    1.Safety Important safety instructions – Save these instructions There exists dangerous voltage and high temperature inside the UPS. During the installation, operation and maintenance, please abide the local safety instructions and relative laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instructions.
  • Page 5: 2.Main Features

    2.Main Features 2.1 Summarization This series UPS is a kind of three-in- single -out high frequency online UPS. The products are modularized and adopt the N+X redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.
  • Page 6: 3.Installation

    3.Installation 3.1 Unpack checking 1. Don’t lean the UPS when moving it out from the packaging 2. Check the appearance to see if the UPS is damaged or not during the transportation, do not switch on the UPS if any damage found. Please contact the dealer right away. 3.
  • Page 7: Pdu Module Outlook (Optional)

    3.3 PDU Module Outlook (Optional) Front View Rear View Side View (1)Mains Breaker (2)Bypass Breaker (3)Maintenance Breaker (4)Output Breaker (5)handles (6) Output(to UPS Output) (7) MAINTAIN-AUXSWS(to UPS MAINTAIN-AUXSWS) (8)Input/ Output Terminal 3.4 LCD control panel LCD control panel introduction (1)LED(from top to bottom: ―alarm‖, ―bypass‖, ―battery‖, ―inverter‖) (2)LCD display (3)scroll button (4)Off button (5)On button(battery cold start switch)
  • Page 8: Installation Notes

    3.5 Installation notes ◆Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas and liquid, corrosive objects. To avoid from high room temperature, a system of room extractor fans is recommended to be installed. Optional air filters are available if the UPS operates in a dusty environment.
  • Page 9 ◆ Over-current Protection device shall be installed at the distribution panel of the incoming main supply. It may identify the power cables current capacity as well as the overload capacity of the system. The following table shows the recommended capacity of the UPS input/output breaker. Please choose as needed.
  • Page 10: Power Cable Connect

    CAUTION! Protective earth cable: Connect each cabinet to the main ground system. For Grounding connection, follow the shortest route possible。 WARNING! FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES MAY RESULT IN ELECTROMAGNETIC INTERFERENCE OR IN HAZARDS INVOLVING ELECTRIC SHOCK AND FIRE 3.8 Power cable connect Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.
  • Page 11 Three phase in single phase out Single phase in single phase out WARNING! In the case of ―split bypass‖ operation, make sure the cable or copper wire between each input lines have been removed. The AC input and the AC bypass supplies must be referenced to the same neutral point. WARNING! If the load equipment is not ready to accept power on the arrival of the commissioning engineer then ensure that the system output cables are...
  • Page 12: Battery Connection

    Power distribution mode for I/O system There are four ways to connect the input and output cables according to the power distribution requirements of users: Three-in single out same source single input (default); three-in single out different source dual input; single in single out same source single input; single in single out different source dual input When selecting different wiring methods, modify the short connected copper bars according to the wiring method below.
  • Page 13: Ups Multi-Module Installation

    Note: The BAT+ of the UPS connect poles is connected to the anode of the positive battery, the BAT-N is connected to the cathode of the positive battery and the anode of the negative battery, the BAT- is connected to the cathode of the negative battery. Factory setting of the long-run unit is battery quantity---16pcs, battery capacity---12V40AH (charger current 6A).
  • Page 14: Parallel Cable Installation

    Make sure each UPS input breaker is in ―off‖ position and there is no any output from each UPS connected. Battery groups can be connected separately or in parallel, which means the system itself provides both separate battery and common battery. WARNING! Make sure the N、...
  • Page 15: Computer Access

    3.11 Computer access ◆One end of a USB cable connect to the computer, the other end connect to the USB port on the UPS. ◆Open the software Muser4000, click ―system‖ button. ◆A window of ―Software Parameter Setting‖ comes out as below, COM choose according to the UPS , baud rate choose 9600, protocol choose ―HIP‖, then save this setting.
  • Page 16 ◆Put the UPS name into ―Equipment Name‖, and UPS’ ID address into ―Equipment address‖. ◆Click the button ―Append‖, then the connection between UPS & computer is accomplished. CAUTION! When the UPS worked on inverter. If you want to use PC to set the output voltage and frequency.
  • Page 17: 4.Operation

    4.Operation 4.1 Operation Modes The UPS is a double-conversion on-line UPS that may operate in the following alternative modes: ◆Normal mode The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter while floating and boosting charge the battery simultaneously. Then, the inverter converts the DC power to AC and supplies to the load.
  • Page 18: Turn On/Off Ups

    ◆ECO Mode When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set at ECO mode in order to increase the efficiency of the power supplied. At ECO mode, the UPS works at Line-interactive mode, so the UPS will transfer to bypass supply.
  • Page 19: Black(Cold) Start Procedure

    ◆ Set the Battery Breaker to the ―ON‖ position according to the user’s manual. ◆ Switch ON UPS input switch. CAUTION! Check to see if the load is safely connected with the output of the UPS. If the load is not ready to receive power from the UPS, make sure that it is safely isolated from the UPS output terminals The internal fan of the UPS starts spinning, the UPS is performing self-diagnostics until buzzer beeps twice to show the UPS is normal.
  • Page 20: Inverter Off

    4.2.4 Inverter Off When the Utility is normal, press ―Off‖ button for approx. 1 sec until beep sounds, the inverter LED will extinguish, the bypass LED on, then the UPS turns to bypass supply. When the UPS is on battery mode or without AC, press ―Off‖ button for approx. 1 sec until beep sounds, the output of the UPS is off, fan stop spinning.After 60 seconds, all the LED on the LCD display extinguish.
  • Page 21 ◆Click ―Set‖ at ―User Set‖ window; ◆At the window of ―Data Set‖, click ―Work Mode‖,, choose ―Parallel‖ for the value, then click ―Set‖ as shown in below picture. If the UPS sounds a ―beep‖, that means the setting is correct. ◆At the window of ―Data Set‖, click ―Ups ID‖, write a value for the parallel UPS ID at the right side, such as ―1‖, then click ―Set‖...
  • Page 22: The Display

    CAUTION! After changing the parallel system ID, the connection between Muser4000 and equipment might be interrupted. If it occurs, please re-connect in accordance with the instruction described before. CAUTION! Parallel cable cannot be connected when setting the parallel parameters. ◆After setting the UPS needed to be paralleled, power off all the UPS. Connect all the UPS according to ―parallel cable installation‖, and then power on the UPS .
  • Page 23 There are 12 interfaces available in the LCD display: Item Interface Description Content Displayed CODE Operational status and mode Input A(Input L1) Voltage & Frequency Input B(Input L2) Voltage & Frequency Input C(Input L3) Voltage & Frequency Bat. + Voltage & Current Bat.
  • Page 24 4. Phase C (L3) Input/Frequency 5. Bat + (Positive) 6. Bat - (Negative) 7. Backup time 8. Output Voltage/Frequency 9. Load Capacity...
  • Page 25 11. Software version & model 10. Temperature (battery/Internal and ambient temperature) 12. Alarm Code If has battery charging, above 2-13 interface windows will also display the charging status at the same time as below: Charging Status Boost Floating 3) Pressing ―scroll‖ button, you may circulate all messages from the first one to the last one then returns back to the first one and vice versa.
  • Page 26: Parameters Setting

    4.4 Parameters setting The setting function is controlled by 3 buttons (, OFF, ON) : ---goes into the setting page and value adjustment; OFF---for exit setting; ---for choosing different pages. After the UPS turn ON, press buttons ―‖ & ―OFF‖ for 2 seconds and then goes into the setting interface page.
  • Page 27: Frequency Setting

    4.4.3 Frequency setting Frequency setting (Note: Inside the broken-line is the flashing part.) In the output voltage setting press ―ON‖ or in battery capacity setting press ―OFF‖, it goes to the frequency setting. The frequency line flashes as in above picture. ①Use button ―‖ to choose the different frequency.
  • Page 28: Battery Quantity Setting

    4.4.5 Battery quantity setting Battery quantity setting (Note: Inside the broken-line is the flashing part.) In the battery capacity setting press ―ON‖ or in bypass voltage upper limit setting press ―OFF‖, it goes to the battery quantity setting. The battery quantity line flashes as in above picture. ①Use button ―‖...
  • Page 29: Bypass Voltage Lower Limit Setting

    4.4.7 Bypass voltage lower limit setting Bypass voltage lower limit setting (Note: Inside the broken-line is the flashing part.) In the bypass voltage upper limit setting press ―ON‖ or in parallel ID setting press ―OFF‖, it goes to the bypass lower limit setting. The bypass lower limit line flashes as in above picture. (―-‖ for negative, positive does not have any symbol.) ①Use button ―‖...
  • Page 30: Periodical Battery Self-Test Setting

    4.4.9 Periodical battery self-test Setting Periodical battery self-test setting (note: the part in dashed box flashes) In the buzzer setting press ―ON‖ or in parallel ID setting press ―OFF‖, it goes to the battery self-test setting. In the meantime the setting state flashes as above picture shows (Note: ON 1- the battery self-test function is enabled, UPS will do self-test 10 seconds every 30 days;...
  • Page 31: Parallel Id Setting

    4.4.11 Device address setting Device address setting(Note: the information in the red box will be flashing) Press ―ON‖ under the battery temperature compensation sensor switch setting or press ―OFF‖ under parallel ID set- ting, goes to the device address setting. The setting state flashes as above picture shows (Note: device address is1~15, it is the MODBUS device address at RS232 &...
  • Page 32: Parallel Quantity Setting

    4.4.13 Parallel quantity setting Parallel quantity setting (Note: Inside the broken-line is the flashing part.) When under the parallel ID setting press ―ON‖ or when under parallel redundancy quantity setting press ―OFF‖, it goes to the parallel quantity setting. The parallel quantity flashes as in above picture. ①Use button ―‖...
  • Page 33: Parallel System Commissioning

    4.5 Parallel system commissioning Parallel system should be commissioning when the stand-alone are all intact. Take 4 units in parallel for example. 1) Confirm the input/output wires connection and input phase sequence are correct; switch off the battery breaker, and measure the +/- bat voltage of all battery group are normal. 2) Connect the parallel cable, it should be formed loop connection。...
  • Page 34: Display Messages/Troubleshooting

    4.6 Display Messages/Troubleshooting This section lists the event and alarm messages that the UPS might display. The messages are listed in alphabetical order. This section is listed with each alarm message to help you troubleshoot problems . Display messages Operational Status and Mode(s) item Content Displayed alarm...
  • Page 35: Options

    DC Bus below voltage Beep continuously Fault LED lit DC bus unbalance Beep continuously Fault LED lit Soft start failed Beep continuously Fault LED lit Rectifier Over Temperature Twice per second Fault LED lit Inverter Over temperature Twice per second Fault LED lit Input neutral loss Twice per second...
  • Page 36 In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is setup for web-based auto language detection.
  • Page 37: Appendix 1 Specifications

    Appendix 1 Specifications MODEL 6kVA 10kVA Capacity (VA/Watts) 6k/6k 10k/10k INPUT 380/400/415Vac,(3Ph+N+PE) Nominal voltage 220/230/240Vac,(L+N+PE) Operating voltage range 208~478Vac Operating frequency range 40Hz-70Hz ≥0.99 Power factor Harmonic distortion (THDi) 3% (100% non-linear load) Max. voltage:220V: +25%(optional +10%,+15%,+20% ) ; 230V: +20%(optional +10%,+15% ) ; Bypass voltage range 240V: +15%(optional +10%) Min.
  • Page 38: Appendix 2 Problems And Solution

    -25℃~55℃ Storage temperature Humidity range 0~95% (non-condensing) Altitude < 1500m Noise level <53dB <55dB PHYSICAL Dimension D×W×H (mm) 443x131(3U)x580 mm Net weight (kg) STANDARDS Safety IEC/EN62040-1,IEC/EN60950-1 IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC6100 0-4-5,IEC61000-4-6,IEC61000-4-8 Appendix 2 Problems and Solution In case the UPS cannot work normally, it might be wrong in installation, wiring or operation. Please check these aspects first.
  • Page 39: Appendix 3 Rs232 Communication Port Definition

    Set the UPS working mode to The UPS is set to ECO mode, The UPS only works on UPS type(non-parallel) or to or the transfer times to bypass bypass mode reset the times of transferring mode are limited. to bypass or re-start the UPS Battery switch is not properly Close the battery switch: closed:...
  • Page 40: Appendix 4 Rs485 Communication Port Definition

    Appendix 4 RS485 communication port definition Definition of port : Connection between the Device’s RS485 port and UPS RS485 port. device(RJ45) UPS(RJ45) Description 485+ ―A‖ Pin 1/5 Pin 1/5 485 - ―B‖ Pin 2/4 Pin 2/4 Pin7 Pin7 +12Vdc Pin8 Pin8 Available function of RS485 ◆...
  • Page 41: Appendix 5 Bat_T Communication Port Definition

    Appendix 5 BAT_T communication port definition Definition of port : Connection between the Temperature senator RJ45 port and UPS RJ45 port. Temperature senator(RJ45) UPS BAT_T(RJ45) Description Pin 1/5 Pin 1/5 Pin 2/4 Pin 2/4 Pin 7 Pin 7 Pin 8 Pin 8 Available function of BAT_T ◆Battery environment temperature monitoring.
  • Page 42: Appendix 6 Output Port Definition

    Appendix 6 Output port definition Definition of port : Connection diagram: Function description: Connect to the Output port on external PDU module (optional), UPS will detect the Output beaker status(ON/OFF) in PDU module to control the inverter output in parallel mode.
  • Page 43: Appendix 7 Maintain-Auxsws Port Definition

    Appendix 7 MAINTAIN-AUXSWS port definition Definition of port : Connection diagram: Function description: Connect to the MAINTAIN-AUXSWS port on external PDU module (optional), UPS will turn off inverter and transfer to inner BYPASS when it detects the Maintenance Breaker is activated.
  • Page 44: Appendix 8 Epo Instruction

    Appendix 8 EPO instruction Definition of port : Connection diagram: Connection between the button and UPS EPO port. Button UPS EPO Description Pin 1 Pin 1 Pin 2 Pin 2 ◆A remote emergency stop switch (Dry contact signal and ―normally open‖ - not provided) can be installed in a remote location and connection through simple wires to the EPO connector.
  • Page 45: Appendix 9 Bms Communication Port Definition (Optional)

    Appendix 9 BMS communication port definition (Optional) Definition of port : Connection between the Lithium battery BMS equipment RJ45 port and UPS BMS RJ45 port. Lithium battery BMS (RJ45) UPS BMS RJ45 Description Pin 1 Pin 2 485+ ―A‖ Pin 3 Pin 3 485+ ―A‖...