2KVA(S)-6batt /3KVA(S): 1. ACinput 2. Network/Fax/ModemSurgeProtection(option) 3. Inputcircuitbreaker 4. EPO(option) 5. USBcommunicationport(option) 6. RS-232communicationport 7. SNMPintelligentslot(option) 8. Outputreceptacles 9. BatteryTerminal 10. OutputTerminal 2-3 Setup the UPS Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
Page 8
For socket-type outputs, simply connect devices to the outlets. For terminal-type input or outputs, please follow below steps for the wiring configuration: a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm power cords for 3KVA (200/208/220/230/240VAC models).
7. Specification MODEL 1KVA(S) 1KVA(H) 2KVA(S) 2KVA(H) 3KVA(S) 3KVA(H) PHASE Single phase with ground Capacity (VA/Watts) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W INPUT Nominal voltage 200/208/220/230/240VAC 160Vac±5% @100%-80% load; 140Vac±5% @80%-70% load; Low line 120Vac±5% @70%-60% load; transfer 110Vac±5% @60%-0% load;...
Page 24
Numbers Backup time Long run unit depends on the capacity of external batteries Typical recharge 4 hours recover to 90% capacity (Typical) time(standard modle) 109. 27.4 41.0 27.4 41.0 54.7 82.1 54.7 82.1 82.1 109.4 82.1 Charging voltage ±1% ±1% ±1% ±1% ±1%...
Need help?
Do you have a question about the UDC9101S One and is the answer not in the manual?
Questions and answers