ELECTRICAL INSTALLATION

8.1 General
The Remeha Quinta 30 is supplied as standard with electronic control and flame
ionisation safety controls with a specially designed microprocessor at the heart of the
control system.
8.2 Specifications
8.2.1 Electrical supply
The Remeha Quinta 30 must have a permanent 230V-50Hz single phase supply rated
at 6.3 Amps. The control unit is not phase / neutral sensitive.
8.2.2 Control box
Manufacture:
Model:
Supply voltage:
Electrical rating:
Pre-purge time:
Post-purge time:
Safety time:
Anti-hunting time:
Pump run on (HTG):
Pump run on (DHW):
8.2.3 Fuse specification
The boiler is protected by fuses:
- on the main power supply located in the euro connector socket rated at 6.3 amps
(slow acting). Spare fuse is supplied - located in the euro connector socket
- control circuit 230 Volt - located on the Gasmodul control box, ref. F1 rated at 2
amps (fast acting)
- control circuit 24 Volt dc- located on the Gasmodul control box, ref. F2 rated at 3.15
amps (slow acting)
Spare fuses are supplied - located on the Gasmodul control box cover.
Gasmodul
MCBA 1461 D
230 V/50 Hz
10 VA
3 seconds
10 seconds
3 seconds
150 seconds
1 - 15 minutes
5 minutes