7.6 Modular systems

The Quinta series of boilers are idealy suited for modular applications. Kits for up to 5
units are available from Broag. Please see separate leaflet for more details.
8

ELECTRICAL INSTALLATION

8.1 General

The Remeha Quinta 45 and 65 is supplied as standard with electronic control and
flame ionisation safety controls with a specially designed microprocessor at the heart
of the control system.

8.2 Specifications

8.2.1 Electrical supply

The Remeha Quinta 45 and 65 must have a permanent 230V-50Hz single phase sup-
ply rated at 6.3 Amps. The control unit is not phase / neutral sensitive.

8.2.2 Control box

Manufacture:
Model:
Supply voltage:
Electrical rating:
Pre-purge time:
Post-purge time:
Safety time:
Anti-hunting time:
Pump run on (HTG):
Pump run on (DHW):

8.2.3 Fuse specification

The boiler is protected by fuses:
- on the main power supply located in the euro connector socket rated at 6.3 amps
(slow acting). Spare fuse is supplied - located in the euro connector socket
- control circuit 230 Volt - located on the Gasmodul control box, ref. F1 rated at 2
amps (fast acting)
- control circuit 24 Volt dc- located on the Gasmodul control box, ref. F2 rated at 4
amps (slow acting)
Spare fuses are supplied - located on the Gasmodul control box cover.
Gasmodul
MCBA 1461 D
230 V/50 Hz
10 VA
3 seconds
10 seconds
3 seconds
150 seconds
1 - 15 minutes
5 minutes