Frequency Setting Function - Panasonic VF100 Instruction Manual

Table of Contents

Advertisement

Frequency
When frequency is set to "digital setting with operation panel (P004=1)", and parameter P040 is set
to "11", SW3 and SW4 can be used to change frequency and SW5 can be used to save this frequency.
•E
Frequency is forced to become function input terminal of "SW3: frequency increase SW",
"SW4: frequency decrease SW" and "SW5: frequency memory SW" after parameter P040
is set to "11".
•E
SW3: During ON, frequency increases. (During OFF, existing frequency is held.)
•E
SW4: During ON, frequency decreases. (During OFF, existing frequency is held.)
•E
SW5: Turn ON once, then turn OFF to save the current frequency.
(This frequency will be saved even if the power is turn OFF.)
SW3(¡ø)
ON
SW4(¨‹)
SW5(memory)
Note1) Turn
button (SW3) and
operation frequency will not be changed.
Note2) When "frequency memory operation of SW5" and "frequency setting in the frequency setting
mode" on the operation panel are not applied, operation frequency will not be saved.
Note
•EON/OFF state of each SW can be set to A contact input or B contact input with parameter "P041:
Input logic setting". When using each SW function, please take note of the setting value of
parameter P041.
88
setting function
Save the frequency when SW5
switches from ON to OFF.
B
A
ON
ON
button (SW4) "OFF" or "ON" simultaneously (A, B area, etc.),
Digital setting frequency on
the operation panel
(Fr mode)
Frequency changed or
saved with
¡¾Terminal connection¡¿
ON
and
button.
SW3
6
7
SW4
8
SW5
9
Common
Related
P004
parameters