P092: Output Ry Function Select - Panasonic VF100 Instruction Manual

Table of Contents

Advertisement

P092£ºOutput RY function select
Used to set the functions of the relay output (control terminals A, B and C).
•E
Energize in ON-state: The relay is turned ON when the coil is excited.
•E
Non energize in ON-state: The relay is turned ON when the coil is not excited.
Setting data
Energize
Non
in
energize
on-state
in on-state
0
r0
Run signal
Reverse
1
r1
run signal
2
r2
Arrival signal
Overload
3
r3
alarm
Frequency
4
r4
detect
Current
5
r5
detect (1)
Current
6
r6
detect (2)
7
r7
Fault alarm (1)
8
r8
Fault alarm (2)
End of timer's
one cycle
9
r9
operation
End of timer's
10
r10
operation
Note
•E Retardation time of current detect signal set to "5" and "6" can be set with "P096: Retardation
time of current detect".
•E Setting data "10" is used to output the time set with "P070: Continuous wait time of timer's operation".
106
(The signal ON-state= Across terminals A-C: ON, across terminals B-C: OFF)
(The signal ON-state= Across terminals A-C: OFF, across terminals B-C: ON)
Function
ON when run signal is ON or during inverter output
ON when the inverter is running in reverse
ON when the output frequency is within the setting
frequency ¡À2Hz
ON when the output current is 140% of the rated current or
higher or when the electronic thermal level is reached.
ON when output frequency is higher than detect frequency
(parameter P094 setting )
ON when output current is higher than detect current level
(parameter P095 setting)
ON when output current is lower than detect current level
(parameter P095 setting )
ON when the inverter is in the fault trip state
ON when the inverter is in the normal state
(OFF when the inverter is in the fault trip state)
ON when timer operates one cycle (only output during wait time)
ON when timer's operation ends (when "tEnd" is displayed)
Conditions for relay to turn ON
Related
parameters
P070
¡«
P094
P096