n014£ºPID setting value (SP)
n015£ºPID measured value (PV)
n016£ºPID output value (MV)
Indicates setting value(SP), measured value(PV) and output value(MV) under PID
control. The unit is "%".
n017£ºProgress of automatic tuning
When automatic tuning is set with P106: PID control mode, the progress of the automatic
tuning is displayed. The initial value is "0" and "1" to "5" is displayed according to progress.
When the automatic tuning ends, the display will return to initial value "0".
"0" to "5" : during measure; "6": measure ends (End) ; "7": measure stops (Err)
n018£ºAccumulative operation time
n019£ºAccumulative fan operation time
Monitor n018 indicates the accumulative time of the inverter when the power supply is
turned ON. Monitor n019 indicates the accumulative time of the cooling fan in the inverter
to operate. P143: cooling fan ON-OFF control is set to"1": In association operation, no
counting will be carried out when the cooling fan is stopped. Display unit is one hour ="0.001".
Displays in 10 hours after "10.00" according to "0.01", in 100 hours after "100.0" according
to "0.1" and in 1000 hours after "1000" according to "1".
As a certain number of errors are available in the details of display, the display can only
be used as reference value.
n020£ºFault display 1 (latest)
n021£ºFault display 2 (second to latest)
n022£ºFault display 3 (third to latest)
n023£ºFault display 4 (fourth to latest)
Indicates the latest, second to latest, third to latest and fourth to latest errors of the inverter.
52