[Operating procedure of automatic tuning]
¢Ù Switch to automatic tuning mode setting
•E When voltage compensation constant is measured : P132 is set to "1"
•E When slip compensation frequency is measured : P132 is set to "2"
¢Ú Enter measurement preparation completed state
Press the MODE SW and enter operation status display
mode.
•EWhen voltage compensation constant is measured,
P132 = "1" is displayed.
•EWhen slip compensation frequency is measured,
P132 = "2" is displayed.
¢Û Start of automatic tuning
Press the RUN SW and automatic tuning is started.
•EWhen voltage compensation constant is measured,
£- Inverter will automatically apply DC high-voltage
to the motor and such operation will last about 2
seconds.
P132 = "1" is displayed in measurement. (flicker)
•EWhen slip compensation frequency is measured,
£- Inverter will drive the motor at 60Hz.
Such operation will last normal 1
plus about 5 seconds.
P132 = "2" is displayed in measurement. (flicker)
¢ÜEnd of automatic tuning
When automatic tuning ends, data will be automatically
written in P133 or P134 and it indicates the end of
automatic tuning.
•EWhen voltage compensation constant is measured,
it indicates the end of measurement.
•EWhen slip compensation frequency is measured, it
indicates the end of measurement.
¢Ý Enter operation preparation completed state (normal
stopped state)
Press the STOP SW and enter the operation preparation
completed state.
After such operation, normal operation can be applied.
st
acceleration time
131