P133£ºVoltage compensation constant
Data value is used to set voltage compensation constant required by vector control.
Data setting value (V)
Calculate the setting data value of voltage compensation constant according to method as below.
Setting value = R¡ÁI
Note
•E When the setting value is relatively large, current trip may occur.
•E When the setting value is relatively small, torque may be inadequate at low speed.
P134£ºSlip compensation frequency
Data value is used to set slip compensation frequency required by vector control.
Data setting value (Hz)
Converting slip at 60Hz to frequency value for setting slip compensation frequency.
Calculate the data according to the method as follow.
Setting value £½
Note
•EWhen the setting value is relatively large, rotation number of motor may be larger than the target.
•EWhen the setting value is relatively small, rotation number of motor may be smaller than the target.
0.01 to 99.99 (0.01 unit)
R : Includes one-phase resistance value of wiring resistance
(1/2 of measured resistance value among motor terminals)
I : Equivalent current (Equivalent to inverter rated current of
motor capacity)
Motor capacity
Equivalent current (A)
0.4kW
0.75kW
1.5kW
2.2kW
3.7kW
-5.00 to 5.00 (0.01 unit)
N0£-N1
¡Á 60(Hz)
N0
1.6
2.1
4.0
6.0
9.4
Related
parameters
120¡Á60
N0 £º
No. of motor poles
N1: Rated rotation number of motor (at 60Hz)
Related
parameters
¡«
Ïà¹Ø
P129
P132
²ÎÊý
P134
Ïà¹Ø
¡«
P129
P133
²ÎÊý
133