7.9 Condenser Protection /
Condenser Protection
Condenser Alarm Limit
Condenser Block Limit
Condenser OK limit
Condenser Low Limit
Con
ERC menu
Default
Min
code
Con
CAL
80/176
0/32
CbL
85/185
0/32
CoL
60/140
0/32
CLL
5
-20/-4
1 Click: Temperature setpoint
Sub function: Up
Condenser Alarm Limit / CAL
This parameter sets the temperature for the condenser at which an alarm will
1 Click: Temperature setpoint
Sub function: Up
be generated .
Condenser Block Limit / CbL
1 Click: Temperature setpoint
This parameter sets the temperature which if reached will cause the compressor
Sub function: Up
1 Click: Temperature setpoint
to switch off .
Sub function: Down
Condenser OK Limit / CoL
This parameter sets the temperature at which the compressor is allowed to
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
start again after the temperature set in CbL above has been exceeded and the
Sub function: Down
compressor stopped .
Condenser Low Limit / CLL
This parameter sets the lowest (condenser) temperature at which the
1 Click: Temperature setpoint
compressor is allowed to start .
Sub function: Down
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Up
NOTE:
A condensor temperature sensor is
required to use these parameters.
Condenser protection is generally used in dusty
environments where the condenser may accumu-
late a layer of dust or dirt and therefore be at risk of
overheating .
Max
Unit
Unit
Conv
1 Click: Temperature setpoint
85/185
C/F a
°C/°F
Sub function: Down
85/185
C/F a
°C/°F
85/185
C/F a
°C/°F
20/68
C/F a
°C/°F
ERC 102 Reference manual – 7 PARAMETERS
Scale
Default Access
Shop Ser OEM
1
-- -- RW
1
-- -- RW
1
-- -- RW
1
-- -- RW
39