Defrost
Def . type
Def terminate temp
Def Min Interval
Def Max Interval
Def Min Time
Def Max time
Drip off time
Fan delay after Defrost
Fan start Temp
Defrost Fan on
Initial Defrost Interval
Defrost on compressor
time
Fan
Fan always On
Fan On Delay
Fan Stop delay
Fan On Cycle
Fan Stop Cycle
Energy management
Shop Light Day
Shop Light Night
Eco Activity delay
Eco Light delay
Eco Temperature Offset
46
ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST
ERC menu
Description
code
dEF
Defrost Settings
dFt
no: Defrost function is disabled
EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details)
nat:Off-cycle defrost (natural defrost)
dtt
Temperature at which defrost cycle will stop
dii
The minimum time in hours between the start of each defrost cycle
dAi
The maximum time in hours between the start of each defrost cycle
dit
The minimum duration of a defrost cycle in minutes
dAt
The maximum duration of a defrost cycle in minutes
dot
The duration in minutes of the drip-off time at the end of a defrost cycle
Fdd
The duration in minutes before the fan starts after a defrost cycle
Ftd
The temperature at which the fan will start after a defrost
dFA
Whether the fan will run during a defrost cycle
idi
The number of hours after power-up before the first defrost cycle starts
dCt
Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
ERC menu
Description
code
FAn
Fan settings
FAo
nO: fan parameters below active . yES: Fan is always on
Fod
Delay in seconds before fan starts after compressor starts
FSd
Delay in seconds before fan stops after compressor stops
FoC
The number of seconds the fan runs when the compressor is off
FSC
The number of seconds the fan does not run when the compressor is off
ERC menu
Description
code
Eng
Energy Management
SLd
When ambient light is above this level, Eco mode is cancelled . Requires light sensor
SLn
When ambient light is below this level, Eco mode is enabled . Requires light sensor
EAd
Minutes delay after last door opening until ECO mode is enabled; 0: disable
ELd
Delay [min] between detection of shop light on/off and ECO mode activation / suspension
Eto
Temperature increase for Eco mode relative to normal mode