4.3.15 Group B Screen 2
'Group B Screen 2' screen panel comes out when DOWN (
panel. Configureations for data management and operation of the main controller are set in this
screen panel.
When touching any button in the screen panel, 10KEY screen comes out for inputting values.
(1) Soft LOCK: Stop modifying data.
(2) Initialization: Return the currently set values to initial values. Also clears the history of
functional failures and warings. But, accumulated operating time and power-on time are not
initialized.
0: [Displays 'NON'] No initialization.
1: [Displays 'Trip'] Initializes history of system failures and warnings.
2: [Displays 'Para'] Initializes set values (parameters).
3: [Displays 'TIME'] Initializes time.
4: [Displays 'All'] Initializes all.
(3) Cell bypass: Enables cell bypass function that make derating operation start.
0: [Displays 'OFF'] when the cell is broken, it motors inverter FREE RUN.
1: [Displays 'ON'] when the cell is broken, cell bypass function enables derating.
(4) Protection: Cancels some protective functions that interrupt normal functional tests.
0: [Displays 'OFF'] Normal protection is running.
1: [Displays 'ON'] Cancels some protective functions for normal functional test.
(5) CELLs per phase: Sets the number of cells for one phase. 3300V or 6600V is always the input
voltage for N5000 inverter. When 3300V is the input voltage, set it 3 in this item. When 6600V
is the input voltage, set it 6 in this item.
(6) Controller mode: If 1 MCU board consists main controller, set it 1. (Displays 'single'). If 2 MCU