7.0 Using an AGS Module: Operating/Monitoring
AGS: 01 AGS Control Menu
This menu is used to enable the AGS (selecting Enable or Enable
w/QT). A "Test" setting is also available to ensure the start/stop wiring from
the generator to the ME-AGS-N is correct. The available settings are:
OFF – This option disables the AGS's generator start/stop functions. It
also turns the generator off if it is running from an autostart command.
When OFF is selected, the generator will not start automatically. This is
the default setting. If you have an AGS fault, select OFF to clear it.
Info: If DC power is lost to the remote or to the system, this menu
resets to the default OFF position for safety.
Enable – Select this option to have the AGS monitor temperature (04
Start Temp F) and/or the inverter's battery voltage (05 Start Volts) to
determine when to automatically start the generator.
Test – Select this option to test the generator. This option starts the
generator, runs it for approximately 30-60 seconds, and then stops the
generator. Use this setting for testing generator wiring and operation.
After a successful start/stop sequence test, this selection returns to OFF.
Enable w/QT – Select this option to have the AGS monitor temperature
(04 Start Temp F) and/or the inverter's battery voltage (05 Start Volts)
to determine when to automatically start the generator—with the Quiet
Time parameters enabled.
WARNING:
garage or any other type of enclosed structure without proper ven-
tilation. Carbon monoxide, an odorless, colorless, deadly gas may
accumulate and cause serious injury or death.
7.3.2

Monitoring the AGS using the ME-RC

The following menus are helpful for the proper operation and monitoring
of your AGS/generator system. Press the AGS button, and then rotate and
press the SELECT knob to access the following menus:
AGS: 02 AGS Status Menu
This menu allows you to view the AGS's current status. There are 14
different status messages to identify the AGS's current state, but only one is
displayed at any one time (refer to Figure 7-2).
Available statuses are (refer to Tables 7-3 thru 7-5 for detailed descriptions
of each):
AC In
Manual Run
No Comm
Info: This menu is important when determining if the AGS is working
correctly, or for troubleshooting an AGS installation.
Info: For any fault mode displayed in the status menu, please refer
to Section 7.8.3 "Resolving Fault Statuses" in this manual.
Note: AGS menus 03-07 were covered in Section 7.1.
63
Never allow the generator to start/run in an enclosed
Off
Quiet Time
Ready
©2013 Magnum Energy, Inc.
Start Temp
Fault Temp
Start Test
Fault Test
Start VDC
Fault VDC
Fault Gen Run
Lockout