Figure 5-8, Bulk Charging Mode; Figure 5-9, Charger Standby Mode; Figure 5-10, Charging Mode - Magnum Energy ME-RC Owner's Manual

Standard remote control
Hide thumbs Also See for ME-RC:
Table of Contents

Advertisement

PWR
FAULT
Bulk Charging
CHG
Settings/Info..
INV

Figure 5-8, Bulk Charging Mode

Bulk Charging – The battery charger is delivering maximum current
(determined by the SETUP menu's 05 Charge Rate setting) to the batteries.
The charger will remain in Bulk Charge until the absorb voltage (determined
by the SETUP menu's 04 Battery Type setting) is achieved.
PWR
FAULT
Charger Standby
CHG
Settings/Info..
INV

Figure 5-9, Charger Standby Mode

Charger Standby – This means the charger has been disabled to
prevent any charging, but the AC power (from shore/utility or generator)
to the AC input is still available on the AC output. This display is shown
when the ON/OFF CHARGER button is pressed while the AC power is passing
through the inverter/charger.
Info: To enable charging again, press the ON/OFF CHARGER button.
When the charger is again enabled, the charger will continue in the
Charge mode it last left and the CHG (green) LED will come on solid.
PWR
FAULT
Charging
CHG
Settings/Info..
INV

Figure 5-10, Charging Mode

Charging – Once Charging mode has been enabled, the unit will wait and
display "Charging" to determine the charge routine. If the DC voltage is low
( 12.8 VDC/12-volt models,
volt models), the charger will initiate Bulk Charging. If the DC voltage is
high (>12.8 VDC/12-volt models, >25.6/24-volt models or >51.2/48-volt
models), the charger will skip the Bulk and Absorb charging stages and go
directly to Float Charging.
©2013 Magnum Energy, Inc.
Bulk Charging appears on LCD.
PWR (green) is on solid, and CHG
(green) LED is typically on solid, but
may blink. FAULT (red) LED is off. INV
(green) LED could be on or off.
Charger Standby appears on LCD.
PWR (green) LED is on solid and CHG
(green) LED blinks. FAULT (red) LED
is off, and INV (green) LED could be
on or off.
Charging appears on LCD. PWR
(green) and CHG (green) LEDs are
on solid. FAULT (red) LED is off, and
INV (green) LED could be on or off.