Table 3-4, Battery Type To Charge Voltages - Magnum Energy ME-RC Owner's Manual

Standard remote control
Hide thumbs Also See for ME-RC:
Table of Contents

Advertisement

3.0 Setup
Info: The voltage settings shown in Table 3-4 are based on the Bat-
tery Temperature Sensor (BTS) at a temperature of 77° F (25° C),
or not connected. If the BTS is connected, the actual charge voltage
will increase if the temperature around the BTS is below 77° F (25°
C), and decrease if higher than 77° F (25° C). This ensures the bat-
teries receive the correct charge voltage regardless of temperature.

Table 3-4, Battery Type to Charge Voltages

Battery
Inverter
Type
Voltage
12 VDC
GEL
24 VDC
48 VDC
12 VDC
Flooded
24 VDC
48 VDC
12 VDC
AGM 1
24 VDC
2
48 VDC
12 VDC
AGM 2
24 VDC
3
48 VDC
Note¹: Voltage same as absorption voltage—to prevent equalization.
Note²: Charge voltages for Concord (Lifeline Series) AGM batteries.
Note³: Charge voltages for East Penn, Deka, Discover and Trojan AGM batteries.
Battery Type (CC/CV) –
Current/Constant Voltage (CC/CV) charging method with an adjustable
charge voltage and a setting that limits output current—if needed. It
consolidates all the battery charge settings that are required for a 2-stage
charging cycle (i.e., Constant Current and Constant Voltage).
Note: The CC/CV settings only display if CC/CV has been selected from
the 04 Battery Type
Info: If 04 Battery Type is set to CC/CV, the following menus are
no longer accessible and display "CC/CV Controlled" when selected:
03 Absorb Time, 05 Charge Rate, and 09 Final Charge. This is to
prevent charging confl icts that could occur while in the CC/CV profi le.
Max Amps – Sets the maximum charge amperage allowed to charge
the batteries during the CC/CV charge cycles. The range of settings
are provided to limit the charge current to the battery bank, which
helps prevent battery overheating caused by charging at too high a
charge rate.
Default: 200 ADC
Range: 20 - 990 ADC
Chg Volts – Sets the voltage level at which the charger will hold
the batteries during the Constant Voltage cycle.
Default:
13.8 VDC (12v), 27.6 VDC (24v), 55.2 VDC (48v)
Range: OFF, 12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0
VDC (48v)
21
Absorption
Voltage
Voltage
14.1 VDC
13.6 VDC
28.2 VDC
27.2 VDC
56.4 VDC
54.4 VDC
14.6 VDC
13.4 VDC
29.2 VDC
26.8 VDC
58.4 VDC
53.6 VDC
14.3 VDC
13.1 VDC
28.6 VDC
26.2 VDC
57.2 VDC
52.4 VDC
14.5 VDC
13.5 VDC
29.0 VDC
27.0 VDC
58.0 VDC
54.0 VDC
The CC/CV selection provides a Constant
menu.
©2013 Magnum Energy, Inc.
Float
Equalization
Voltage
14.1 VDC
28.2 VDC
56.4 VDC
15.5 VDC
31.0 VDC
62.0 VDC
15.5 VDC
31.0 VDC
62.0 VDC
14.5 VDC
29.0 VDC
58.0 VDC
1
1
1
1
1
1