Errors Related To Unit Configuration - Omron NJ501-1 Series User Manual

Machine automation controller nj-series cpu unit hardware
Table of Contents

Advertisement

Event code
Event name
1004 0000 hex
SD Memory
Card
Restored or
Formatted
1006 0000 hex
SD Memory
Card Data
Corrupted
1007 0000 hex
SD Memory
Card Access
Power OFF
Error
1031 0000 hex
Incorrect SD
(Ver. 1.02)
Memory Card
Removal

Errors Related to Unit Configuration

Event code
Event name
0401 0000 hex
I/O Bus
Check Error
2401 0000 hex
Unsupported
Unit Detected
NJ-series CPU Unit Hardware User's Manual (W500)
Meaning
Assumed cause
An error was
• The Controller power supply
detected during the
was turned OFF while the SD
file system check
BUSY indicator was lit.
and the file system
• The power supply to the Con-
was restored. Files
troller was interrupted momen-
may have been
tarily while the SD BUSY
deleted.
indicator was lit.
• The SD Memory Card was
removed while the SD PWR
indicator was lit.
• The SD Memory Card is dam-
aged.
A file that must be
• The Controller power supply
in the SD Memory
was turned OFF while the SD
Card is missing or
BUSY indicator was lit.
corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the SD BUSY
indicator was lit.
• The SD Memory Card was
removed while the SD PWR
indicator was lit.
• The SD Memory Card is dam-
aged.
The power supply
• The Controller power supply
to the Controller
was turned OFF while the SD
was interrupted
BUSY indicator was lit.
during access to
• The power supply to the Con-
the SD Memory
troller was interrupted momen-
Card.
tarily while the SD BUSY
indicator was lit.
SD Memory Card
• The SD Memory Card was
removal process-
removed while the SD PWR
ing failed.
indicator was lit.
Meaning
Assumed cause
An error occurred in
• The I/O Connecting Cable is
a bus line transmis-
disconnected or wires inside it
sion between the
are broken.
CPU Unit and the
• Conductive material has gotten
Units in the rack
inside.
slots. Or, detection
• The connector contact is faulty
of all Special I/O
due to foreign material in the
Units and CPU Bus
connector.
Units was not com-
• Noise
pleted when the
• A Unit has failed.
power supply to the
Controller was
turned ON.
An unsupported
• An unsupported CJ-series Unit
CJ-series Unit or
or Power Supply Unit was
Power Supply Unit
detected.
is mounted.
5 Troubleshooting
Level
Maj
Prt
Min
Obs Info
U
S
page 5-32
U
S
page 5-33
S
page 5-33
S
page 5-34
Level
Maj
Prt
Min
Obs Info
S
page 5-35
S
page 5-36
Reference
5
Reference
5-15

Advertisement

Table of Contents
loading

Table of Contents