&RPSRQHQWV
Reference
Manual
068' 31 $ 
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The
D350RP includes an alarm relay.
Heat Detectors
The H350 is an intelligent heat detector with a thermistor sensing circuit for fast
response, designed to provide open area protection with 50 foot (15 m) spacing
capability. The H350R incorporates a thermal Rate-of-Rise circuit of 15
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder
base for intelligent, addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke
detectors. It may be used to control auxiliary functions.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It
functions similar to the I300 isolator module which allows loops to operate under fault
conditions and automatically restore when the fault is removed.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface
between the control panel and conventional notification and initiating devices. Each
module can be set to respond to an address with built-in rotary switches. A blinking
LED on a monitor module indicates communication between the module and the
control panel. These devices can also be used when installed on older systems. Refer
to the Fire•Lite Device Compatibility Document for a list of approved notification and
initiating devices.
Monitor Modules
The MMF-300, MMF-300-10, MDF-300, MMF-302 and MMF-302-6 are addressable
monitor modules for monitoring conventional initiating devices. The MMF-300 is used
for normally open contact alarm initiating devices, such as manual pull stations, four-
wire smoke detectors, heat detectors, waterflow, security contacts and supervisory
devices. The MMF-300-10 functions the same as the MMF-300 except it provides 10
Class B or 5 Class A inputs. The MDF-300 is a dual monitor module (Class B only)
which occupies two consecutive SLC addresses, with each module functionally the
same as the MMF-300. The MMF-302 is used primarily for two-wire smokes detectors
in addition to normally open contact devices. The MMF-302-6 functions the same as
the MMF-302 except it provides 6 Class B or 3 Class A inputs. The supervised IDCs
(Initiating Device Circuits) can be wired to the modules as NFPA Style B (Class B) or
Style D (Class A) circuits. The modules are supplied with a thermoplastic cover for
mounting to a 4-inch mounting box.
Monitor Module (miniature)
The addressable MMF-301 module is functionally similar to an MMF-300 but offered
in a smaller package for mounting directly in the electrical box of the monitored device.
Control Module
The CMF-300 and CMF-300-6 are an addressable Control Modules used to connect
NACs (Notification Appliance Circuits) to power and supervise compatible, UL-listed
notification appliances. The CMF-300 provides one Class B or Class A output while
the CMF-300-6 provides 6 Class B or 3 Class A outputs. The NACs can be wired to the
module as supervised NFPA Style Y (Class B) or Style Z (Class A) circuits. The
modules are supplied with a thermoplastic cover for mounting to a 4-inch square
mounting box.