Fire-Lite MS-9200UD User Manual page 39

Fire alarm control panel
Hide thumbs Also See for MS-9200UD:
Table of Contents

Advertisement

Optional Module Installation
4XTMF
MS-9200UD PN 51906:A 12/10/02
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secodary) from the FACP before installing
4XTMF
2. Cut jumper JP3 on the main circuit board to allow the control panel to supervise
the 4XTMF module
3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6
on the MS-9200UD main circuit board, being careful not to bend any pins
4. Secure 4XTMF module to standoffs with supplied screws.
5. Reapply power to the FACP
6. For proper 4XTMF operation, the output relays must be programmed for the
factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
7. When the installation has been complete, enable the 4XTMF module by sliding
the disconnect switch to the left
8. Test system for proper operation
TB5
NO NC C
Standoff
RELAY 1
JP1
J5 & J6 Connectors
1 2 3
MS-9200UD
Figure 2.5 4XTMF Connectors to MS-9200UD Connectors
NOTE: Jumper JP2 on the MS-9200UD main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be
programmed as a supervisory relay.
Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens
SLC
SLC
SLC
SLC
SHIELD
TB6
TB8
TB9
TB10
NO NC C
OUT+ IN+ OUT- IN-
ACS
B+ A+ B- A-
A
Standoff
RELAY 2
JP2
4XTMF
J6
J5
JP3
CUT TO
MONITOR
4XTMF
J7
SEC. ACTIVE
PRI. ACTIVE
J13
J12
PRI. PHONE LINE
SEC. PHONE LINE
Installation
B
Cut Jumper JP3
KISSOFF
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200ude

Table of Contents