NFPA Standard-Specific Requirements
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module
Polarities shown in alarm condition
176
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for
separate transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to
Municipal Box.
2. Cut JP3 on the MS-9200UD main circuit board to supervise placement of
4XTMF module and circuit.
3. Cut JP2 on the MS-9200UD main circuit board to enable FACP Supervisory
relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed
information.
Figure C.4 Municipal Box Connected to 4XTMF Transmitter Module
Municipal Box
Circuit
Gamewell Model M34-56
Local Energy Municipal Box
Nonpower-limited
-
+
4XTMF
MS-9200UD PN 51906:A 12/10/02
Correlations