Process Monitor Operation

4.7 Process Monitor Operation

4.8 Hazard/Tornado Condition Operation

4.9 Medical Alert Condition Operation

4.10 NAC Operation

MS-9200UD PN 51906:A 12/10/02
Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type,
address, adjective/noun, associated zones and time/date
Communicate the process monitor condition to the Central Station
Relays programmed for process monitoring will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Note that, like supervisories, process monitor signals latch (except when programmed
for process monitor autoresettable) and can be assigned to software zones.
Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ½ second On, ½ second Off
The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date
Communicate the hazard condition to the Central Station
Relays programmed for hazard will be activated
The alarm relay is not activated
Silenced alarms are resounded
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Hazard conditions latch. They can be assigned to software zones.
Medical Alert Condition operation will initiate the following events:
The piezo sounder ½ second On, ½ second Off
The LCD displays a medical alert message along with the device name, type,
address, adjective/noun, associated zones and time/date
Communicate the medical alert condition to the Central Station
Relays programmed for medical alert will be activated
The alarm relay is not activated
Silenced alarms are resounded
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Medical alert conditions latch. They can be assigned to software zones.
There are four Style Y (Class B) or two Style Z (Class A) programmable NACs
(Notification Appliance Circuits) resident on the MS-9200UD main circuit board. All
NACs may be programmed as silenceable or nonsilenceable and may also be
programmed for steady or coded operation. Coded operation provides a choice
between March Time, Temporal or California coding.
Operating Instructions
135