Optional Modules

Cabinet
The cabinet is red and the backbox measures 20.00" (50.8 cm) long X 17.00" (43.18 cm) high X 3.125"(7.938
cm) deep and provides space for two batteries (up to 7 Amp Hours). Also included is a dress panel, DP-2410BC,
which comes premounted inside the cabinet.
MS-2410BC Cabinet
FIGURE 1-5:
Transformer Assembly
One 100VA transformer is provided standard with the panel.
An optional 100VA transformer, XRM-24, is available to
provide maximum accessory power.
Batteries
The cabinet provides space for 7 Amp Hour batteries (larger
batteries up to 18 Amp Hour batteries, use the listed Fire•Lite
BB-17F battery box). Batteries must be ordered separately.
1.6
Optional Modules
LED-10IM
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator,
LDM Series Annunciator, AFM Series Annunciator and ACM-8RF Relay Modules. EIA-485 wiring is
supervised for short, open and grounded circuits by this module. The LED-10IM mounts to connector J5 on the
main circuit board.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists.
1.7

Optional Accessories

Dress Panel
A red dress panel (DP-2410BC) is supplied and is required for Canadian installations. The dress panel restricts
access to the system wiring while allowing access to the membrane switch panel. Refer to Figure 1-1, "DP-
2410BC," on page 7.
12
FIGURE 1-6:
Standard XRM-24
Optional XRM-24