Optional Modules

The MP-12/24 will accept one of the following optional modules:
• Dry Alarm Contacts (MP-AC12; MP-AC24). Two Form-C rated 3 A @ 120 VAC and 30 VDC (resistive).
• Dry Alarm and Trouble Contacts (MP-AT12; MP-AT24). One Form-C Alarm and one Form-C Trouble,
both rated 3 A @ 120 VAC and 30 VDC (resistive).
• Remote Station Output Modules Models MP-TRT12 and MP-TRT24 output alarm and trouble. Models
MP-TR12 and MP-TR24 output alarm only.
Activation: By any zone alarm.
Disconnect: By an internal service switch, off-normal switch produces audible and visual trouble signals.
Remote Station Type: (MP-12) 12 VDC polarity reversal; (MP-24) 24 VDC polarity reversal.
Internal Resistance of Remote Station Output: (MP-12) 112 ohms; (MP-24) 660 ohms.
Ripple Voltage: Less than 2.0 Vp-p.
(Not suitable for separate transmission of both alarm and trouble signals to Remote Station).
System Control Switches
• Reset
• Trouble Silence
• Disable
System Status Indicators
• Red Zone alarm LED.
• Yellow system trouble LED.
• Green AC power LED.
Transformer
Harness
Connector
AC Circuit
Breaker
Primary
AC Power
+ -
- + -
Alarm
Notification
Initiating
LEDs
Appliance
Device
Circuit
Circuits
Reset
Switch
Figure 3.1: Component and Terminal Locations
MP-12/24 Fire Alarm Control Panel
Optional Module
Connector
AC Power
Trouble
LED
LED
Disable
Trouble
Switch
Silence
Switch
Document 15440:G
6/6/96
Battery
Connector
7