APPENDIX D
CIRCUIT CONNECTIONS
Circuit Type
Circuit Function
SLC loop
Connects to
(power-limited)
Addressable
Devices
ACS/TERM
Connects to
(EIA-485)
annunciator
(power-limited)
modules
EIA-232
connects to
(power-limited)
remote printer
and PC computer
MMF-300 and
Initiating Device
MMF-301
Circuit
(power-limited)
MMF-302
Initiating Device
(power-limited)
Circuit
CMF-300
Notification
(power-limited)
Appliance
Circuit
24 VDC
Connects to
filtered
4-wire smoke
resettable
detectors
(power-limited)
24 VDC
Connects to
nonresettable
control modules,
(power-limited)
annunciators and
accessories
CHG-120F or
Remote
CHG-75
secondary power
source
Table Footnote
1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
MS-9200UD PN 51906:A 12/10/02
Wire Requirements
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The
total resistance of any branch cannot exceed 40 ohms. The total wire length of all
branches cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the MS-9200UD main circuits must be
carefully considered to ensure proper operation. It is important to use the correct type
of wire, wire gauge and wire run length for each MS-9200UD circuit. Reference the
chart below to specify wire requirements and limitations for each MS-9200UD circuit.
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the
risk of encountering problems can be greatly reduced by exclusively employing
electronic sounders (such as MA/SS-24D) instead of more electronically noisy
notification appliances such as electromechanical bells or horns.
Table D.1 MS-9200UD Wire Specifications
Wire Type and Limitations
Twisted, shielded pair, 40
ohms maximum per length
of Style 6 and 7 loops. 40
ohms per branch maximum
1
for Style 4 loops
Untwisted, unshielded pair
Twisted, shielded pair with a
characteristic impedance of
120 ohms
Twisted, shielded pair
Maximum loop wire
resistance is 40 ohms for the
MMF-300 and 20 ohms for
the MMF-301
No more than a 2.4 volt drop
allowed at end of circuit.
Maximum loop wire
resistance is 25 ohms
In alarm, no more than a 1.2
volt drop allowed at end of
circuit
No more than 1.2 volt drop
allowed from supply source
to end of any branch
No more than 1.2 volt drop
allowed from supply source
to end of any branch
2
12 AWG (3.25 mm
) in
conduit
WIRE REQUIREMENTS
Recommended
Max. Distance
Wire Gauge and Compatible Brands
Feet (meters)
10,000 (3,000 m)
12 AWG (3.25 mm
8,000 (2,400 m)
Signal 98230, Belden 9583, WPW999
4,875 (1,450 m)
14 AWG (2.00 mm
3,225 (980 m)
Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm
6,000 (1,800 m)
18 AWG (0.75 mm
50 (15 m)
18 AWG (0.75 mm
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 1.2 volt
maximum line
drop
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 1.2 volt
maximum line
drop
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 1.2 volt
maximum line
drop
20 (6 m)
12-18 AWG (3.25 - 0.75 mm
Wire Requirements
2
): Genesis 4410,
2
):Genesis 4408 & 4608
2
): Genesis 4406 & 4606
2
): Genesis 4402 & 4602
2
)
2
)
2
) minimum
2
)
2
)
2
)
2
)
2
)
2
)
179