Programming
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
122
3.7.1 Disable Point
Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the
following screens to be displayed:
POINT PROGRAM
1=DETECTOR
2=MODULE
Select the device type by pressing 1 for an addressable detector or 2 for an addressable
module. The operator will be prompted to enter the three digit device address as shown
in the following example for a detector:
EDIT DETECTOR
ENTER POINT ADDRESS
***
A flashing cursor will appear in the bottom left corner of the display, prompting for the
three digit device address. When the third digit is enter, 001 for example, a screen will
appear which will allow enabling or disabling of the selected point, as illustrated in the
following example:
EDIT DETECTOR 1D001
1=ENABLED
Enable/Disable Select Screen
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled
No.
Maintenance Programming Level
Device Select Screen
Address Select Screen
YES
MS-9200UD PN 51906:A 12/10/02