0DVWHU 3URJUDPPLQJ /HYHO
MONITOR TYPE
1=POWER-MONITOR
2=TROUBLE-MONITOR
3=USER-DEFINED-12
Monitor Type Screen #9
MONITOR TYPE
1=PROC-MON
2=PROCMON-AR
3=USER-DEFINED-13
Monitor Type Screen #10
Note: For the PROCMON-AR selection, PROCMON refers to Process Monitor and AR refers to AutoResettable
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
Blank
User-Defined-3
Future Use
User-Defined-4
Smoke-Conventional
Heat-Detector
User-Defined-5
User-Defined-6
Medic-Alert
User-Defined-7
Hazard-Alert
User-Defined-8
Tornado-Alert
User-Defined-9
User-Defined-10
User-Defined-11
Tamper
Supervisory
Supervisory-AR
Power-Monitor
Trouble-Monitor
User-Defined-12
Proc-Mon
Procmon-Auto
User-Defined-13
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
User-Defined-14
068' 31 $ 
:KLOH YLHZLQJ RQH RI WKH 0RQLWRU 7\SH VFUHHQV VHOHFW WKH W\SH RI PRQLWRU PRGXOH
EHLQJ SURJUDPPHG E\ SUHVVLQJ WKH FRUUHVSRQGLQJ NH\SDG QXPEHU NH\ 7KH GLVSOD\
ZLOO UHWXUQ WR WKH (GLW 0RQLWRU 6FUHHQ  ZKLFK ZLOO VKRZ WKH QHZ W\SH VHOHFWLRQ
0RQLWRU PRGXOH W\SH VHOHFWLRQ ZLOO DIIHFW WKH IXQFWLRQ RI WKH SRLQW DV IROORZV
Action When Activated
Fire Alarm
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm
Fire Alarm
Fire Alarm
Future Use
Supervisory on partial short, Fire Alarm on full short
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Supervisory, nonlatching (tracking)
Supervisory, latching
Supervisory, nonlatching (tracking)
AC Fault
Trouble
Trouble
Piezo
Piezo, nonlatching (tracking)
Piezo, nonlatching (tracking)
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
PAS Disable
MONITOR TYPE
1=ACK-SWITCH
2=SIL-SWITCH
3=RESET-SWITCH
Monitor Type Screen #11
MONITOR TYPE
1=DRILL-SWITCH
2=PAS-BYPASS
3=USER-DEFINED-14
Monitor Type Screen #12