2: Intelligent Addressable Modules: Newer Series; 3: 300 Series Intelligent Addressable Devices - Fire-Lite MS-9200(C) Instruction Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200(C):
Table of Contents

Advertisement

Components
1.5.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the control panel and con-
ventional notification and initiating devices. Each module can be set to respond to a maximum address of 99 with
built-in rotary switches. A blinking LED on monitor modules indicates communication between the module and the
control panel. Refer to the Fire•Lite Device Compatibility Document for a list of approved notification and initiating
devices.
Monitor Modules
The MMF-300, MDF-300 and MMF-302 are addressable monitor modules that can be used to monitor conventional
normally open contact alarm initiating devices, such as manual pull stations, 4-wire smoke detectors, heat detectors,
waterflow and supervisory devices. The MDF-300 is a dual monitor module in a single package (Class B only) with
each module functionally the same as the MMF-300. The MMF-302 is used primarily for two-wire smoke detectors
in addition to normally open contact devices. The supervised IDCs (Initiating Device Circuit) can be wired to the
module as NFPA Style B (Class B) or Style D (Class A). The modules are supplied with a thermoplastic cover for
mounting to a 4-inch mounting box.
Monitor Module (miniature)
The MMF-301 is an addressable monitor module that is a miniature version of the MMF-300. It connects with wire
pigtails (Style B [Class B] only), and may be mounted directly in the electrical box of the device being monitored.
Control Module
The CMF-300 is an addressable control module used to connect NACs (Notification Appliance Circuits) to power
and supervise compatible UL-listed notification appliances. The NACs can be wired to the module as supervised
NFPA Style Y (Class B) or Style Z (Class A) circuits. The modules are supplied with a thermoplastic cover for
mounting to a 4-inch square mounting box.
Relay Module
The CRF-300 is an addressable control relay module which is functionally similar to the CMF-300 but used as a
Form-C relay module
Manual Pull Station
The BG-12LX is an addressable manual pull station featuring key-lock reset. The pull station responds to an address
set by the installer using the built-in rotary decimal switches on the pull station. The manual pull station includes a
Fire•Lite key. The BG-12LX address module LED condition is visible through the translucent handle.
I300
The loop isolator module is an automatic switch which opens the circuit voltage to the SLC Loop branch(es) when-
ever a wire-to-wire short circuit is detected on that loop. The remainder of the communications loop leading up to the
I300 will continue to operate, unaffected by the short. The isolator module is bi-directional, meaning that it can
detect a fault condition between the input SLC terminals or output SLC terminals. The I300 is required to meet
NFPA Style 7 requirements.
1.5.3 300 Series Intelligent Addressable Devices
Fire•Lite's legacy 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200 FACP.
Compatible devices include:
• SD300: Photoelectric Smoke Detector
• SD300T: Photoelectric Smoke Detector with Thermal Sensor
• CP300: Ionization Smoke Detector
• M300: Monitor Module
• M301: Miniature Monitor Module
• M302: two-wire Monitor Module
• C304: Control/Relay Module
• BG-10LX Manual Pull Station
Document #51003
Rev.E
01/11/02
P/N 51003:E
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200e

Table of Contents