3: 300 Series Intelligent Addressable Devices; 4: Addressable Device Accessories - Fire-Lite MS-9200UD User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9200UD:
Table of Contents

Advertisement

3URGXFW 'HVFULSWLRQ

Relay Module
The CRF-300 and CRF-300-6 are a Control Relay Modules which are functionally
similar to the CMF-300 but used as Form-C relay modules. The CRF-300 provides one
Form-C relay while the CRF-300-6 provides six Form-C relays.
Isolator Module
The I300 loop isolator module is an automatic switch which opens the circuit voltage to
the SLC loop branch(es) whenever a wire-to-wire short circuit is detected on that loop.
The remainder of the communications loop leading up to the I300 will continue to
operate, unaffected by the short. The isolator module is bidirectional, meaning that it
can detect a fault condition between the input SLC terminals or output SLC terminals.
The I300 is required to meet NFPA Style 7 requirements.
Detector Annunciator
The RA400Z is a remote single LED annunciator that can be wired directly to an
addressable detector for annunciation of that detector's alarm status.
Manual Pull Station
The BG-12LX is an addressable manual pull station featuring a key-lock reset. The
pull station responds to an address set by the installer using the built-in rotary decimal
switches on the pull station. The manual pull station includes the Fire•Lite key.
1.6.3 300 Series Intelligent Addressable Devices
Fire•Lite's 300 Series Intelligent Addressable Devices are fully compatible with the
MS-9200UD FACP. The address of 300 Series devices cannot be set above 99.
Compatible devices include:
SD300 Photoelectric Detector
SD300T Photoelectric Detector with Thermal Sensor
CP300 Ionization Detector
M300 Monitor Module
M301 Miniature Monitor Module
M302 2-wire Monitor Module
C304 Control/Relay Module
BG-10LX Manual Pull Station
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly Fire•Lite P/N R-47K
The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the
MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-
Line Resistor assembly is used to supervise the MMF-302 module circuit. The resistors
are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-
wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate. An ELR, which is supplied with each
module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to
the N-ELR plate can be used for the supervision of a monitor and control module
circuit.