Step 6. Installing LED/Switch Modules into Expansion Bays,
LED/Switch
Controller Card,
(continued)
Configuring the
LED/Switch
Controller Card
Mounting

LED/Switch Modules

to the Expansion
Bay
LOCKWASHERS
If more than 32 zones are required, a second controller (4100-1289) will be required.
Note that an ME0456 fan control module counts as 8 zones when adding up the controller
requirements.
LED 1. This LED illuminates if communication loss between the controller and the CPU
occurs. It is independent of jumper P1 (which configures different communication loss
features).
The 64/64 LED/switch controller requires physical configuration, but the LED/Switch
modules do not. Switch controller configuration consists of setting jumper P1 and setting
the card address. See Figure 2-12. In the 4100ES-S1, the first display controller is
address 3 and the second has address 4. Card addressing is covered in Appendix A.
Refer to Figure 2-13 to mount the display cards to the front of the expansion bay.
ADDITIONAL
LED/SWITCH
CONTROLLER
#6 UNC NUTS

Figure 2-13. LED/Switch Card Mounting

GROUND
CONNECTION
2-19
Continued
GROUND
CONNECTION
LED/Switch Controller
assemblies are installed
in the end slot in the
basic 4100U-S1
Continued on next page