Class B Nac Wiring Table - Simplex 4100ES-S1 Installation & Maintenance

Fire indicator panel
Hide thumbs Also See for 4100ES-S1:
Table of Contents

Advertisement

Power Supply Wiring Distances,
Class B NAC
Wiring Table
Alarm
Current @
0.75 mm
24V
0.25A
230m
0.50A
120m
0.75A
1.00A
1.25A
1.50A
1.75A
2.00A
2.25A
2.50A
2.75A
3.00A
Table 5-2 lists the maximum distances from the NAC terminal block to the last appliance
in a Class B (string) configuration, depending on wire gauge and current. Use Table 5-2
to calculate wire distances for your application if you are using Class B wiring.
Table 5-2. Class B (string) Wiring Distances
2
2
1.00 mm
310m
150m
77m
100m
58m
77m
46m
62m
38m
51m
33m
44m
29m
38m
26m
34m
23m
31m
21m
28m
19m
26m
Notes:
Max Distance = distance from SPS to last appliance.
This table is calculated at 49 degrees Centigrade.
Distances are based on a 3V drop, and take into account the worst-case panel
output voltage. These distances are based on the worst case of having one single
load at the furthest point.
If circuit integrity wire is used instead of housing cable in a fire rated enclosure,
reduce wiring distances by 12 m for every 3 m of potential exposure.
Continued
2
1.50 mm
2.50 mm
460m
770m
230m
380m
150m
260m
120m
190m
92m
150m
77m
130m
66m
110m
58m
96m
51m
85m
46m
77m
42m
70m
38m
64m
5-7
2
2
4.00 mm
Resistance
1200m
12.0 ohms
620m
6.0 ohms
410m
4.0 ohms
310m
3.0 ohms
250m
2.4 ohms
210m
2.0 ohms
180m
1.7 ohms
150m
1.5 ohms
140m
1.3 ohms
120m
1.2 ohms
110m
1.1 ohms
100m
1.0 ohms
DC