4100ES-S1 Specifications
System Capacity
Expansion
Cabinet Size
Cabinet Material
Cabinet Finish
Cabinet Colour
Mounting
Mains Input
Internal Power Supply
Standby Battery
Battery Charger
PSU Supervision
Temperature
Humidity
Refer to Table 4-1 and 4-2 for full SPS specifications.
Alarm Relay Card:
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board:
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
WALK TEST System Test
4 Operator Access Levels
Event Historical Logging
Device selectable Alarm Verification
Individual Zone Isolate
Addressable device disable/enable
Non-volatile Flash EPROM for field editable program changes
Expansion cards firmware upgraded via download to flash EPROMs
500 points of addressable devices, plus 500 points of
annunciation.
up to 4 x 4100 legacy cards
up to 4 x 4" x 5" PDI cards
1050H x 550W x 280D (mm)
1.2mm Zintec
Powder coated
Cream Wrinkle external, flat black internal trim
Wall mount
240V AC, +6%, -10%, 50Hz
24V DC @ 9A
24V sealed lead acid type up 40Ah
27.3V DC (nominal)
Charger high/low, Battery low/fail
-5C to 45C
10% to 90% RH non-condensing