T-Gen 50 Setting For Relay Operation - Simplex 4100ES-S1 Installation & Maintenance

Fire indicator panel
Hide thumbs Also See for 4100ES-S1:
Table of Contents

Advertisement

Using T-GEN 50 with 4100ES-S1,
T-GEN 50 Setting for
Relay Operation
Table 5-3 shows the switch and link settings for T-GEN 50 software version 1.7 when
controlled from a relay output.
Alert to Evacuate
Change-Over Time
SW1
SW2 (T1)
(T0)
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
SWITCH
Name
SW4
ALM I/P
Supervision
SW5
ALM I/P
SW6
Evac Tone
SW7
SW8
Evac Message
Link
Name
1
BIAS
2
MASTER
3
REC EN
4
TEST
5
SLAVE
6
SLAVE / MASTER
7
FAULT=
DEF-/RELAY
Continued
Table 5-3. T-GEN 50 Settings
SW3
(T2)
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Setting on T-GEN 50
ON (Supervision enabled)
OFF (Non-latching)
OFF for AS 2220 tone
ON for ISO 8201 + Keywords
OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201
Setting on T-GEN 50
FITTED if PA or Background Music not
required.
FITTED
Fit to record message.
Fit for test tone during installation
NOT FITTED
MASTER
RELAY
5-11
Setting on T-GEN 50
0 sec
30 sec
1 min
1.5 min
3 min
5 min
10 min
Alert Only
OFF
Continued on next page