T-Gen 50 Settings For Nac Operation - Simplex 4100ES-S1 Installation & Maintenance

Fire indicator panel
Hide thumbs Also See for 4100ES-S1:
Table of Contents

Advertisement

Using T-GEN 50 with 4100ES-S1,
T-GEN 50 Settings for
NAC Operation
Table 5-4 shows the switch and link settings for T-GEN 50 software version 1.7 when
controlling from a NAC output.
Alert to Evacuate
Change-Over Time
SW1
SW2 (T1)
(T0)
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
SW1 to SW3 settings have no effect on Slave T-GEN 50s.
SWITCH
Name
SW4
ALM I/P
Supervision
SW5
ALM I/P
SW6
Evac Tone
SW7
SW8
Evac Message
Link
Name
1
BIAS
2
MASTER
3
REC EN
4
TEST
5
SLAVE
6
SLAVE / MASTER
7
FAULT=
DEF-/RELAY
Continued
Table 5-4. T-GEN 50 Settings
SW3
(T2)
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Setting on T-GEN 50
OFF (Supervision disabled)
OFF (Non-latching)
OFF for AS 2220 tone
ON for ISO 8201 + Keywords
OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201
Setting on T-GEN 50
Can be FITTED if PA or Background
Music not required
FITTED
Fit to record message.
Fit for test tone during installation
NOT FITTED
MASTER
RELAY
5-13
Setting on T-GEN 50
0 sec
30 sec
1 min
1.5 min
3 min
5 min
10 min
Alert Only
OFF
Continued on next page