7 Precautions for Use of Parameters for Drive Programming
7-1
Inverter Parameters Affected by
Setting Order
In some cases, the setting range of the parameters are restricted by the setting data of other parameters.
The following are the representative examples.
For details, refer to the MX2 User's Manual (I570-E2) or the RX User's Manual (I560-E2).
Parameter
No.
A003
1st Base Frequency
A004
1st Maximum Frequency
A203
2nd Base Frequency
A204
2nd Maximum Frequency
A303
RX only: 3rd Base Frequency
A304
RX only: 3rd Maximum Frequency
A013
FV Start Ratio
A014
FV End Ratio
A103
FI Start Ratio
A104
FI End Ratio
A113
RX only: FE Start Ratio
A114
RX only: FE End Ratio
A020
1st Multi-step Speed Reference 0
A220
2nd Multi-step Speed Reference 0
A320
RX only: 3rd Multi-step Speed Reference 0
A021 to
Multi-step Speed Reference 1 to 15
A035
b015
Free-electronic Thermal Frequency 1
b017
Free-electronic Thermal Frequency 2
b019
Free-electronic Thermal Frequency 3
b051
Starting Voltage on Power Interruption
b052
Deceleration Hold Level on Power Interruption
b060
Window Comparator FV Upper Limit Level
b061
Window Comparator FV Lower Limit Level
b062
Window Comparator FV Hysteresis Width
7 - 2
Description
Data
30. to 1st Maximum Frequency (A004)
MX2: 1st Base Frequency (A003) to 400.
RX: 30. to 400.
30. to 2nd Maximum Frequency (A204)
MX2: 2nd Base Frequency (A203) to 400.
RX: 30. to 400.
30. to 3rd Maximum Frequency (A304)
30. to 400.
0. to FV End Ratio (A014)
FV Start Ratio (A013) to 100.
0. to FI End Ratio (A104)
FI Start Ratio (A103) to 100.
100. to FE End Ratio (A114)
FE Start Ratio (A113) to 100.
0.00/Starting Frequency to 1st Maximum Fre-
quency (A004)
0.00/Starting Frequency to 2nd Maximum Fre-
quency (A204)
0.00/Starting Frequency to 3rd Maximum Fre-
quency (A304)
0.00/Starting Frequency to 1st Maximum Fre-
quency (A004)
0. to Free-electronic Thermal Frequency 2
Free-electronic Thermal Frequency 1 to Free-elec-
tronic Thermal Frequency 3
Free-electronic Thermal Frequency 2 to 400.
0.0 to 999.9/1000.
0.0 to 999.9/1000.
Set an upper limit level.
Setting range: 0. to 100.
Lower limit: Lower limit level (b061)  Hysteresis
width (b062)  2
Set a lower limit level.
Setting range: 0. to 100.
Upper limit: Upper limit level (b060)  Hysteresis
width (b062)  2
Set a hysteresis width for the upper and lower limit
levels.
Setting range: 0. to 10.
Upper limit: (Upper limit level (b060)  Lower limit
level (b061)) /2
Drive Programming User's Manual (I580-E2)