Emc-Correct Electrical Installation - Danfoss VLT HVAC Basic Drive FC 101 Quick Manual

Vlt hvac basic drive fc 101
Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Quick Guide
UL
Power [kW]
3x525-600 V IP20
2.2
3
3.7
5.5
7.5
11
15
18.5
Cutler-Hammer
22
EGE3080FFG
30
37
Cutler-Hammer
45
JGE3125FFG
55
75
Cutler-Hammer
JGE3200FAG
90
3x380-480 V IP54
0.75
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Moeller NZMB1-A125
37
45
Moeller NZMB2-A160
55
75
Moeller NZMB2-A250
90
Table 1.22 Fuses

1.3.7 EMC-Correct Electrical Installation

General points to be observed to ensure EMC-correct
electrical installation.
Use only screened/armoured motor cables and
screened/armoured control cables.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
®
VLT
HVAC Basic Drive Quick Guide
Circuit Breaker
Non UL
Bussmann Bussmann Bussmann Bussmann
Type RK5 Type RK1
FRS-R-80
Cutler-Hammer
FRS-R-80
EGE3080FFG
FRS-R-80
FRS-R-125
Cutler-Hammer
FRS-R-125
JGE3125FFG
FRS-R-125
FRS-R-200
Cutler-Hammer
JGE3200FAG
FRS-R-200
®
MG18A402 - VLT
is a registered Danfoss trademark
Fuse
UL
Type J
KTS-R20
KTS-R20
KTS-R20
KTS-R20
KTS-R20
KTS-R30
KTS-R30
KTN-R80
KTN-R80
KTN-R80
KTN-R125
KTN-R125
KTN-R125
KTN-R200
KTN-R200
high frequencies. Use the cable clamps provided
instead.
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
Use starwashers and galvanically conductive
installation plates.
Do not use unscreened/unarmoured motor cables
in the installation cabinets.
Non UL
Max fuse
Type T
Type G
20
20
20
20
30
35
35
80
80
80
125
125
125
200
200
125
125
125
160
160
200
200
15
1
1

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents