Quick Guide
Alarm/
Warning
Fault
Bit
number
Number Fault text
57
timeout
58
internal
59
25
Current limit
External
60
44
Interlock
Heat sink
Temperature
66
26
Low
Pwr. Card
69
1
Temp
Illegal power
section config-
79
uration
Drive
80
29
initialised
Auto DC
87
47
Braking
95
40
Broken Belt
126
Motor Rotating
200
Fire Mode
Fire Mode
Limits
202
Exceeded
250
New sparepart
251
New Typecode
Table 1.29
®
VLT
HVAC Basic Drive Quick Guide
Trip
Warning Alarm
locked Cause of problem
Try to start the again a number of times, until the is carried out.
NOTE
Repeated runs may heat the motor to a level where the
resistance Rs and Rr are increased. In most cases, however,
this is not critical
X
X
X
Contact the local Danfoss supplier.
X
The current is higher than the value in 4-18 Current Limit
External interlock has been activated. To resume normal operation,
apply 24 V DC to the terminal programmed for external interlock
and reset the frequency converter (via serial communication, digital
X
I/O, or by pressing reset button on keypad).
This warning is based on the temperature sensor in the IGBT
X
module (Only on 400 V 30-90 kW units).
The temperature sensor on the power card is either too hot or too
X
X
X
cold.
X
X
Internal fault. Contact the local Danfoss supplier.
X
All parameter settings are initialized to default settings.
X
The drive is auto DC braking
Torque is below the torque level set for no load, indicating a
X
X
broken belt. See parameter group 22-6*.
X
High back-emf voltage. Stop the motor of the PM motor.
X
Fire mode has been activated
X
Fire Mode has suppressed one or more warranty voiding alarms
The power or switch mode power supply has been exchanged.
X
X
(Only on 400 V 30-90 kW units). Contact the local Danfoss supplier
The frequency converter has a new type code (Only on 400 V 30-90
X
X
kW units). Contact the local Danfoss supplier.
®
MG18A402 - VLT
is a registered Danfoss trademark
1
1
33