Quick Guide
1
1
Power kW
3 x 525 - 600 V
IP20
2.2
3
5.5
7.5
11
15
22
30
45
55
75
90
3 x 380 - 480 V
IP54
0.75
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Table 1.3 Fuses
1.3.7 EMC-Correct Electrical Installation
General points to be observed to ensure EMC-correct
electrical installation.
•
Use only screened/armoured motor cables and
screened/armoured control cables.
•
Connect the screen to earth at both ends.
•
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
16
VLT HVAC Basic Drive Quick Guide
Circuit Breaker
UL
Non UL
Cutler-Hammer
Cutler-Hammer
EGE3080FFG
EGE3080FFG
Cutler-Hammer
Cutler-Hammer
JGE3125FFG
JGE3125FFG
Cutler-Hammer
Cutler-Hammer
JGE3200FAG
JGE3200FAG
Moeller NZMB1-A125
Moeller NZMB2-A160
Moeller NZMB2-A250
MG18A302 - VLT
UL
Bussman
Bussman
n
n
Type RK5 Type RK1
KTS-R20
KTS-R20
KTS-R20
KTS-R20
KTS-R30
KTS-R30
FRS-R-80
KTN-R80
FRS-R-80
KTN-R80
FRS-R-125 KTN-R125
FRS-R-125 KTN-R125
FRS-R-200 KTN-R200
FRS-R-200 KTN-R200
high frequencies. Use the cable clamps provide-
dinstead.
•
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
•
Use starwashers and galvanically conductive
installation plates.
•
Do not use unscreened/unarmoured motor cables
in the installation cabinets.
®
is a registered Danfoss trademark
Fuse
Non UL
Bussman
Bussman
Max fuse
n
n
Type J
Type T
Type G
20
20
20
30
35
35
80
80
125
125
200
200
125
125
125
160
160
200
200
Need help?