Quick Guide
1.3.8 Control Terminals
IP20 200-240 V 0.25-11 kW and IP20 380-480 V 0.37-22 kW:
Illustration 1.22 Location of Control Terminals
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
Illustration 1.23 IP20 380-480 V 30-90 kW
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
Digital input 18, 19 and 27 mode is set in 5-00 Digital Input
Mode (PNP is default value) and digital input 29 mode is
set in 5-03 Digital Input 29 Mode (PNP is default value).
®
VLT
HVAC Basic Drive Quick Guide
Illustration 1.24 IP54 400 V 0.75-7.5 kW
Control terminals
Illustration 1.25 shows all control terminals of the frequency
converter. Applying Start (term. 18), connection between
terminal 12-27 and an analog reference (term. 53 or 54
and 55) make the frequency converter run.
OFF
Illustration 1.25 Control Terminals
®
MG18A402 - VLT
is a registered Danfoss trademark
1.
Remove the front cover.
BUS TER.
ON
61 68 69
18 19
27 29 42 45 50 53 54
0/4-20mA A OUT / DIG OUT
0/4-20mA A OUT / DIG OUT
12 20 55
GND
GND
17
1
1