Emc-Correct Electrical Installation - Danfoss VLT HVAC Basic Drive FC 101 Design Manual

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

How to Install
Power [kW]
3x525-600 V IP20
2.2
3
3.7
5.5
7.5
11
5
5
15
18.5
22
30
37
45
55
75
90
3x380-480 V IP54
0.75
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Table 5.17 Fuses

5.2.5 EMC-Correct Electrical Installation

General points to be observed to ensure EMC-correct
electrical installation.
Use only screened/armoured motor cables and
screened/armoured control cables.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
62
®
VLT
HVAC Basic Drive Design Guide
Circuit Breaker
UL
Non UL
Cutler-Hammer
Cutler-Hammer
EGE3080FFG
EGE3080FFG
Cutler-Hammer
Cutler-Hammer
JGE3125FFG
JGE3125FFG
Cutler-Hammer
Cutler-Hammer
JGE3200FAG
JGE3200FAG
Moeller NZMB1-A125
Moeller NZMB2-A160
Moeller NZMB2-A250
MG18C402 - VLT
UL
Bussmann Bussmann Bussmann Bussmann
Type RK5 Type RK1
Type J
KTS-R20
KTS-R20
KTS-R20
KTS-R20
KTS-R20
KTS-R30
KTS-R30
FRS-R-80
KTN-R80
FRS-R-80
KTN-R80
FRS-R-80
KTN-R80
FRS-R-125
KTN-R125
FRS-R-125
KTN-R125
FRS-R-125
KTN-R125
FRS-R-200
KTN-R200
FRS-R-200
KTN-R200
high frequencies. Use the cable clamps provided
instead.
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
Use starwashers and galvanically conductive
installation plates.
Do not use unscreened/unarmoured motor cables
in the installation cabinets.
®
is a registered Danfoss trademark
Fuse
Non UL
Max fuse
Type T
Type G
20
20
20
20
30
35
35
80
80
80
125
125
125
200
200
125
125
125
160
160
200
200

Advertisement

Table of Contents