User area read/write method

1.12 User area read/write method

Inverter parameters Pr.506 to Pr.515, Pr.826 to Pr.865 can be used as user parameters.
Since this parameter area and the devices used with the PLC function, D110 to D159,
are accessible to each other, the values set in Pr.506 to Pr.515, Pr.826 to Pr.865 can be
used in a sequence program. The result of operation performed in the sequence
program can also be monitored using Pr.506 to Pr.515, Pr.826 to Pr.865.
Inverter
Device
Parameter
No.
No.
D110 to
506 to 515,
D159
826 to 865
Inverter parameters
POINT
Example of using the user parameter area
When the timing is to be changed for machine adjustment using D110 that
stores the timer setting, setting Pr. 506 without modifying the program enters
the set data into D110, enabling adjustment.

1.12.1 User parameter read/write method

User parameter (Pr.506 to Pr.515, Pr.826 to Pr.865) and device (D110 to D159) data can
be read/written freely. Data transfer between Pr.506 to Pr.515, Pr.826 to Pr.865 and D110
to D159 is executed automatically.
1) User parameter write processing and device write processing
When values are written to Pr.506 to Pr.515, Pr.826 to Pr.865 using the FR-PU04/FR-
PU07(-01) or computer link communication, they are written to the parameter
storing RAM area and EEPROM area, and further to D110 to D159 simultaneously.
2) User parameter read processing and device write processing.
When values are written to D110 to D159 from the PLC function side, they are
written to the parameter storing RAM area (Pr.506 to Pr.515, Pr.826 to Pr.865) and
read
using
communication option). (Since data are not written to the EEPROM, making power-
on reset returns the data to the original values.)
3) Processing performed at inverter reset or power restoration
When the inverter is reset, the Pr.506 to Pr.515, Pr.826 to Pr.865 values stored in the
EEPROM are transferred to the RAM area and D110 to D159.
FR-PU04/FR-PU07(-01)
or RS-485 communication
44
Initial
Name
Value
User
parameters
Pr.506 to Pr.515,
Pr.826 to Pr.865
the
FR-PU04/FR-PU07(-01)
1)
Pr.506 to Pr.515,
Pr.826 to Pr.865
(RAM)
2)
Pr.506 to Pr.515,
1)
Pr.826 to Pr.865
(EEPROM)
Setting
Minimum Setting
Range
0 to
0
65535
PLC function devices
D110 to D159
or
1)
3)
Data Access
Unit
1
communication(RS-485
D110 to D159
2)
3)
1)
Always
enabled
or