Series commissioning with the OP

Upload and download a parameter set with an OP
A single parameter set can be uploaded from an inverter and then downloaded into another
inverter.
Note
The following important restrictions should be considered when performing upload and
download:
• Only the parameter set stored in the EEPROM of the inverter is uploaded to the OP.
• Safety parameter cannot be uploaded to the OP.
• Once the upload or download procedure has started, it should not be interrupted.
• It is possible to uplaod data from inverters of different power and voltage ratings.
• During download, if data are not compatible with the inverter, the default values for the
• During the up or download the "RDY" LED (green) is flashing. After finishing that process
• During the upload process any data already held by the OP is overwritten.
• If the download fails, the inverter will not function correctly and the "SF" LED (red) is on.
Notice
After upload and download of parameters between differing Control Units, parameter
settings must be checked.
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
the affected parameter will be written to the inverter.
successfully the "RDY" LED is on.
– Possible fault messages in case of download failure with OP
F0055, F0056, F0057 or F0058
– Possible fault messages in case of download failure with MMC
F061, F0062 or F0063
Commissioning (software)
2.7 Commissioning modes
2-43