Commissioning (software)
2.7 Commissioning modes
Table 2-16
Quick commissioning - flow chart
Parameter
Action/Description (Factory setting: bold)
Parameters with an "*" have more settings than listed below. Please refer to the parameter list
P0003 = 3
User access level*
1: Standard: Allows access into most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0004 = 0
Parameter filter*
0: All parameters
2: Inverter
3: Motor
4: Speed sensor
P0010 = 1
Commissioning parameter filter*
0: Ready
1: Quick commissioning
30: Factory setting
Note: P0010 should be set to 1 in order to parameterize the data of the motor rating plate.
P0100 = 0
Europe/North America (enter the motor frequency)
0: Europe [kW], frequency default, 50 Hz
1: North America [hp]. frequency default, 60 Hz
2: North America [kW], frequency default, 60 Hz
P0205 = 0
Inverter application (enter the required overlaod)
0: High overload (for compressors, processing machines, etc.)
1: Light overload (for pumps and fans, etc.)
Note: This parameter is only effective for Inverters ≥ 5.5 kW/400 V.
P0300 = 1
Select motor type
1: Asynchronous rotational motor
2: Synchronous rotational motor (Note: only V/f control types (P1300 < 20) are permitted)
P0304 = ?
Rated motor voltage (enter value from the motor rating plate in V)
The input of rating plate data must correspond with the wiring of the motor (star/delta). This
means, if delta wiring is used for the motor, delta rating plate data has to be entered.
P0305 = ?
Rated motor current
enter value from the motor rating plate in A
P0307 = ?
Rated motor power
enter value from the motor rating plate in kW or hp
Note: if P0100 = 0 or 2, data is in kW and if P0100 = 1, data is in hp.
P0308 = ?
Rated motor cosPhi (only visible if P0100 = 0 or 2)
enter cosϕ from the motor rating plate.
Setting P0308 = 0 causes internal calculation of value.
P0309 = ?
Rated motor efficiency (only visible if P0100 = 1)
enter value (%) from the motor rating plate.
Setting P0309 = 0 causes internal calculation of value
P0310 = ?
Rated motor frequency
enter value from the motor rating plate in Hz
Pole pair number recalculated automatically if parameter is changed.
P0311 = ?
Rated motor speed
enter value from the motor rating plate in RPM)
Setting P0311 = 0 causes internal calculation of value.
Note: Required for vector control and V/f control with speed controller.
Slip compensation in V/f control requires rated motor speed for correct operation.
P0314 = ?
Motor pole pair number
1: 2-pole motor
2-20
Operating Instructions (Compact), 04/2006, A5E00766042B AA
Your own
setting
Control Units CU240S