Diagnostics using alarm numbers
If a Basic Operator Panel (BOP) is fitted to the Control Unit and a alarm or fault condition
occurs, the BOP will display the appropriate alarm or fault number.
If an alarm occurs, the alarm number will be displayed and the inverter will continue to run,
although it is possible that it may run in an unexpected manner depending upon the alarm
condition.
If a fault occurs, the fault number will be displayed and normally the inverter will be stopped.
Table 5-1
Alarm
Number
A0700
A0702
A0703
A0704
A0705
A0706
A0710
A0711
F0070
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
Alarm numbers, cause and remedy
Meaning
Cause
The parameter or configuring settings by the PROFIBUS master are
invalid.
Remedy
Correct the PROFIBUS configuration
Cause
The link to the PROFIBUS is interrupted.
Remedy
Check connector, cable and PROFIBUS master.
Cause
No setpoints or invalid setpoints (control word = 0) are being received
from the PROFIBUS master.
Remedy
Check setpoints from the PROFIBUS master. Switch SIMATIC CPU to
"RUN".
Cause
At least one configured internode transmitter is not yet active, or has
failed.
Remedy
Activate internode transmitter.
Cause
No actual values received from inverter.
Remedy
None (fault is with the inverter).
Cause
PROFIBUS-DP software error.
Remedy
None diagnostic parameter r2041.
Cause
Inverter has detected failure of PROFIBUS communications link.
Remedy
Communication interface on Control Unit may be broken.
Cause
Invalid value of PROFIBUS parameter.
Remedy
Check P0918 address and P2041.
Cause
No communication via PROFIBUS. Triggered by A0702, A0703 and
A0704. The telegram failure time set in P2040 has run out. Details see
section "Faults and Alarns" in the Parameter List.
Remedy
Check connection of the communication devices and ensure that a
valid control word is being used.
Troubleshooting/FAQs
5-3