Table 2-17 Automatic Download Fault Codes - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

Successful automatic download
After a successful automatic download, F0395 will be displayed.
• In case of a standard CU a confirmation is necessary.
• In the case of CUs with safety integrated functions, an acceptance test must be
Confirmation
On standard CUs the current parameter set needs to be checked and confirmed by clearing
F0395. It can be cleared via:
• Digital input or PLC signal (depends on the settings of P0700)
• setting P7844 = 0.
Acceptance test
On CUs with integrated fail-safe functions it is necessary to do an acceptance test (refer to
the "Safety-Integrated functions" section in this manual). To clear F0395 on CUs with
integrated fail-safe functions the following procedure has to be followed:
• P0010 = 95
• P9761 = fail-safe password
• P7844 = 0
Automatic download fault
If the automatic download process fails, the CU will return to the parameter set previously
held in the EEPROM and the following fault codes are generated:
Table 2-17
Fault code
F0061
F0063
In this case check, wether the MMC is defective or a parameter set clone00.bin is available
or the parameter set is valid.
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
performed.
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Automatic download fault codes
Description
Automatic download of parameters was not successful.
Automatic download of parameters was not successful (e.g. wrong CU).
Commissioning (software)
2.7 Commissioning modes