Table 5-4 Parameter Accessing Error Numbers - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

Table 5-4
Number
0 ... 199:
0
1
2
3
4
5
6
7
11
12
17
101
102
104
106
200/201
240 ... 249:
240
241
242
243
244
248
249
250:
250
251:
251
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
Parameter accessing error numbers
Cause
Parameter access has been converted to a PKW request. Error detected in the
inverter. Additional information is in r2054.05 and r2054.06: Parameter number,
index word
Parameter number does not exist
Parameter number cannot be modified
Minimum/maximum not reached or exceeded
Sub-index does not exist
Access of single value with array identifier
Access to word with double word request or vice
versa
Setting not allowed (resetting only)
Descriptive element cannot be modified
No status as master control
Key word missing
Request cannot be processed due to operating
state
Parameter number currently deactivated
Channel not wide enough
Illegal parameter value
Request not implemented
Modified minimum or maximum not reached or
exceeded.
Parameter access is incorrectly formatted. Error detected on the PROFIBUS DP
Additional information in r2054.05 and r2054.06: Parameter number or S7 data block
number, sub-index or S7 data block offset.
Error in variable address (no additional
information)
Data block number illegally formatted
Data block offset illegally formatted
Illegal "type"
Illegal "Number of elements" on accessing
parameter value
Illegal text/description modification
Inconsistency in write request: "Type" and
"Number of elements" does not match "Data type"
and "Data length"
Parameter access has been converted to a PKW request. Response from inverter is
seen as incorrect. Error detected on the PROFIBUS-DP. Additional information can
be seen in r2054.05 and r2054.06.
PKW response does not match request
Error detected on the PROFIBUS-DP; no additional information
Response too long for response telegram
Troubleshooting/FAQs
Remedy
Check data block number
--
--
Check data block offset
Set data block offset = 0
Use correct data type
(e.g. INT for word, DINT for
double word)
--
--
--
--
--
--
--
--
--
Minimum or maximum can be
further limited in operation
Legal: "Data block" area
Legal: 1 ... 31999
Legal: 0 ... 116
Legal: CHAR, BITE, INT,
WORD, INT, DWORD, REAL
Legal: Effectively 2 or 4 bytes
--
Error in communication device
Error in the inverter
Error in communication device
5-5