Commissioning (software)
2.8 Encoder Commissioning
Table 2-19
Encoder supply
Warning
DIP switches 3 and 4 in ON position provide a supply voltage of 24 V to the encoder.
Therefore it is not allowed to connect a TTL encoder to the inverter if both DIP switches, 3
and 4 are in ON position.
2.8.2

Parameterizing the Encoder Interface

Encoder parameterization
To enable the Encoder to function correctly with the inverter, the parameters in the table
below, must be modified.
Table 2-20
Parameter
r0061
r0090
P0400[3]
r0403
2-56
Encoder voltage settings
On
OFF
3
voltage
Encoder type
No encoder
Encoder parameters
Name
Rotor speed
Rotor angle
Encoder type
Status word of
encoder
Bit 00 - Encoder module active
Bit 01 - Encoder error
Bit 02 - Signal OK
4
3
4
0 V
24 V
HTL encoder
Values
Indicates the speed of the rotor. Used to check that the system is
working correctly.
Indicates the current angle of the rotor. This function is not available on
single input channel encoders.
0: No encoder
2 or12: Quadrature encoder (channel A + B) –
the term "quadrature" means two periodic functions separated by a
quarter cycle or 90 degrees
Displays status word of encoder in bit format:
Operating Instructions (Compact), 04/2006, A5E00766042B AA
3
4
3
5 V
24 V
TTL encoder
HTL encoder
0
1
0
1
0
Control Units CU240S
4
No
Yes
No
Yes
No