specifications
V-ISTA-20HW
1. Physicak
12-W" W x 14-1/2° H x 3" D (318mm x 368mm x 76mm).
SECURITY CONTROL
2. Electrical
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No.
1321/TF2 (in U.S.A.).
RECHARGEABLE
BACK- UP BATTERY:
12VDC, 4AH (Gel type)
minimum. Charging Voltage: 13.8VDC.
ALARM SOUNDER: 12V, 2.o Amp output can drive 12V BELLS or can
drive one or two 702 (series connected) self-contained 20-watt sirens. Do
not connect two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max. Interrupts for 4-
wire smoke detector reset.
Note:
For UL installations, Alarm Sounder plus Auxiliary Power currents
should not exceed 700mA total.
STANDBY TIME: (see formula in Section 13. FINfi
POWER UP for
required battery size needed).
FUSE:
Battery (3A) No. 90-12.
3. Communication:
FORMATS SUPPORTED:
Ademco Express,
10 charactershec, DTMF (TouchTone) D ataTones,1400/2300Hz ACK,
1400Hz KISSOFF.
Ademco Contact ID Reporting,
10 characters/see., DTMF (TouchTone) Data Tones,1400/2300Hz ACK,
1400Hz KISSOFF.
Ademco Low Speed, 10 pulses/see,1900Hz DataTone,
1400Hz ACWKISSOFF.
Radionics/SESCOA 20 pulseshec,1800Hz Data Tone, 2300Hz
ACWKISSOFF. Can report O-9, B-F
Line Seize: Double Pole.
Ringer Equivalence: 0.7B.
FCC Registration No.: AC 398U-68192-AL-E.
4. Maximum Zone Resistance:
Zones 1-8= 300 ohms excluding EOLR
4127
1. Physicak
5-5/8" W x 4-11/16 H x 7/8" D (143mm x l19mm x 22mm).
REMOTE KEYPAD
2. Electrical:
Voltage Input: 12VDC, Current Drain: 20mA.
3. Interface Wiring To controlpanel'skeypadconnection points.
RED:
12VDCinput(+) auxpwr.
GREEN:
Data Outto Control.
YELLOW:
Data In hornControl.
BLACK
Ground.
4137AD & 5137AD
1. Physicak
8-2/5" W x 4-3/4' H x 1-1/10"D (213mmx 121mmx 28mm).
REMOTE KEYPADS
2. Electrical
VoltageInput:
12VDC.
Current Drain:
60mA (4137A.D).
9onA(5137AD).
3. Interface Wiring
RED:
BLUE:
GREEN:
YELLOW
BLACK
12VDC input (+) auxiliary power.
18VDC input from optional No 1350 or 1360 Power Pack
(not usable for UL installations).
Data Out to Control.
Data In from Control.
Ground (–) connection horn optional No. 1350/1360 Power pack.