Commercial burglary partitioned security system with scheduling (72 pages)
Summary of Contents for ADEMCO VISTA-20PS Series
Page 1
9,67$3366HULHV 9,67$36HULHV 6H.XULW\6\VWHPV ,QVWDOODWLRQDQG6HW8S*XLGH AR ME RE AD Y Principal changes from previous version are indicated by margin lines. ® K5305-1V2 1/03...
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Page 4
Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) .........9-3 Creating Schedules ............................10-1 About Schedules............................10-1 System Communication ..........................11-1 Panel Communication with Central Station....................11-1 Report Code Formats............................11-1 Ademco Contact ID ® ............................11-2 System Operation ............................12-1 Security Codes ..............................12-1 Setting the Real-Time Clock ........................12-3 Various System Trouble Displays........................12-4 Testing the System............................13-1 About Test Procedures ..........................13-1...
• Event Logging records selected events in a history log; control and readout from the log is done via Ademco Compass Downloader software or installer/master code at Keypad (VISTA-20P = 100 events; VISTA-15P = 50 events) •...
-- Use any combination of 4204, 4229 and or Powerline Carrier Devices. -- Output functions (up to 48) • Ademco 4285/4286 Phone Module (Part. 1 only); provides access to the system via on premises or off-premises phones for arming, disarming, etc., plus control of relay outputs and Powerline Carrier devices.
S E C T I O N Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices.
Installation and Setup Guide Notes Mounting Board with RF Receiver • Do not mount the cabinet on or near metal a. Remove the receiver board from its case, then objects. This will decrease RF range and/or block insert the top of the board into the slots at the top RF transmissions from wireless transmitters.
Mounting and Wiring the Control Wiring to Keypads Notes • Typical Fixed-Word Display: 6150 Connect keypads to the control’s keypad terminals as • Typical Alpha Display: 6160 shown on the Summary of Connections diagram. • Voice Keypads: 6150V, 6160V Determine wire gauge using the Wiring Run Chart •...
Installation and Setup Guide Notes Sounder (Bell) Connections This control complies with NFPA requirements for 1. Make sounder connections to alarm output terminals temporal pulse sounding of fire notification appliances. 3 (+) and 4 (–). Temporal pulse sounding for a fire alarm consists of: For supervised output, continue with steps 2 and 3.
NP7-12 (two) ‡ 500mA 17.2AH NPG18-12 ‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the panel’s cabinet.) Notes Earth Ground • This product has been designed and laboratory-...
Installation and Setup Guide Hardwire Zones Notes • EOLR: If the EOLR is not at the end of the loop, Normally Open Zones/ Normally Open EOLR Zones the zone is not properly supervised and the 1. Connect open circuit devices in parallel across the system may not respond to an “open”...
Mounting and Wiring the Control Smoke Detectors Notes • Fire Verification (zone type 16): The control 2-Wire Smoke Detectors panel will “verify” a fire alarm by resetting the 1. Connect up to sixteen (10, if “clean me” option used) smoke detectors after the first alarm trigger, and 2-wire smoke detectors across zone 1 terminals 8 (+) then waiting 90 seconds for a second alarm and 9 (-) as shown in the Summary of Connections...
Installation and Setup Guide 4219/4229 Expansion Zones Notes • Supports expansion zones (NO or NC) using 1. Connect each module to the control’s keypad 4219/4229 Zone Expander Modules as follows: terminals. 2. Assign each module a unique device address (07-11) VISTA-20P: Up to 40 expansion zones using up to five Zone Expander Modules.
Mounting and Wiring the Control Notes Installing the RF Receiver • The receiver is supervised and a trouble report is Use any ADEMCO 5800 Series Wireless Receivers, such sent (“CHECK 100” displayed) if communication between the panel and receiver is interrupted, or RF Receiver No.
LOCK BOARD SWITCH (N. O.) • a fire alarm installation, the keyswitch must be located BLUE BLUE next to an alphanumeric display keypad. The Ademco 4146 keyswitch is UL Listed. EOLR (use appropriate value) Figure 10. Keyswitch Wiring Connections 2-10...
Mounting and Wiring the Control Notes Connecting Relay Modules • Use 4204 or 4229 modules. 1. Mount either remotely or in the control panel. 2. Connect to control’s keypad terminals using the • Supervision: 4204 and 4229 modules are connector harness supplied with the module. Use supervised against removal.
Installation and Setup Guide Notes Powerline Carrier Devices • When using Powerline Carrier devices, you must 1. Install the powerline carrier devices according to the use a 4300 or 1321X10 Transformer instead of instructions included with each. the 1321 Transformer. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used) •...
Mounting and Wiring the Control On-Board Triggers Notes • Trigger outputs are normally high, and go low Connect field wiring to the desired trigger pin on the upon programmed condition. 8-pin trigger connector centrally located above the • The outputs can be programmed for inverted terminal strip.
Installation and Setup Guide Notes Phone Line/Phone Module Connections • Use 4285 or 4286 Phone Modules. 1. Connect incoming phone line and handset wiring to Compatibility: 4286 Phone Modules must have the main terminal block (via an RJ31X jack) as software version WA4286-15.1 or higher (refer to shown in the Summary of Connections diagram at the label on the square 4286 microprocessor chip).
E.g., Using output 18 for the trigger, program an UL installations using the AAV feature must use the output function in *80 Menu mode as: ADEMCO UVCM module (part of the ADEMCO UVS ZT = 60, P = 0, Action = 1, Device = 18 system).
S E C T I O N Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation.
Installation and Setup Guide Keypads Keypads are identified by predefined addresses (starting at address 16) as follows: Address Keypad Program Field • always enabled for partition 1, all sounds enabled. keypad 1 NOTE: First keypad is address 16. • data field *190 keypad 2 •...
Programming Overview Function Keys To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
Page 26
Installation and Setup Guide • Usually assigned to a zone containing an emergency button. Type 06 • Sends a report to the central station but provides no keypad display or sounding. 24-hour Silent Alarm • Assign to a zone that has an emergency button. Type 07 •...
Programming Overview • Usually assigned to all sensors or contacts on exterior doors and windows where Type 24 bells and/or sirens are NOT desired. Silent Burglary • Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
Page 28
Installation and Setup Guide Interactive Mode Programming (∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82) Press [ ∗ ] + [Interactive Mode No.] (for example, ∗ 56) while in Program Mode. Entering Interactive Mode The Alpha display keypad will display the first of a series of prompts requesting entries.
S E C T I O N Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION If selected, all messages programmed to go to the primary telephone Long Range Radio Output line receiver will also be sent to the connected 7720PLUS, 7820, 0 = not used 7835, or 7845 Radio (sent in Contact ID format).
ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone until you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again.
Page 33
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Exit Error Report Code After arming the system, zones remaining open after exit delay expires cause an alarm sound at the keypad and external sounder 0 = no report (keypad also displays “EXIT ALARM”), and entry delay begins. 1-F = see description above Disarming before the end of the entry delay stops the alarm sounding and no message is sent to the central station.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Bypass Restore Report Code This is sent when a zone that has been bypassed is unbypassed. UL: Required for UL commercial burglar alarm installations. 0 = no report 1-F = see description above *59 AC Restore Report Code Sent when AC power has been restored after an AC power outage.
Page 35
AWAY. UL installations using the AAV IMPORTANT: AAV should not be used when Paging or Alarm feature must use the ADEMCO UVCM Reports are sent to a secondary number unless the monitoring zone module (part of the ADEMCO UVS option is used (which pauses calls).
Page 36
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Entry 1: Sets the length of time a phone line fault must remain after Phone Line Monitor Enable detected before the second digit option is activated. Entry 1–Timeout: 0 = disabled Entry 2: Selects the desired phone line fault response.
Data Field Programming Pager Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION If you enter fewer than 20 digits, exit by pressing [∗] and next field Pager 1 Phone No. *160 number. To clear entries from this field, press ∗160∗. Enter up to 20 digits Pager 1 Characters Up to 16 optional characters may be sent as a prefix to the 7-digit...
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION See field ∗161 for explanation of entries. If fewer than 16 characters, Pager 2 Characters *164 exit by pressing [∗] and next field number. To clear entries from this Enter up to 16 characters field, press ∗164∗.
Data Field Programming Configurable Zone Type Programming Fields The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90, 91]), based on the options described below. All configurable zone types can be programmed via the downloader.
Page 40
Installation and Setup Guide Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Auto Restore Vent Zone Intact EOL Open Shorted RF zone normal RF zone N/A RF zn off-normal INTACT OPEN SHORTED 0 = normal 0 = normal 0 = normal 0 = no...
Data Field Programming Symphony (AUI) Enable FIELD TITLE and DATA ENTRIES EXPLANATION APPLIES TO VISTA-20PS ONLY. Symphony (AUI) Enable *189 Enter each AUI’s home partition. 0 = disabled AUI 1 address must be set to 1. 1 = partition 1 AUI 2 address must be set to 2.
S E C T I O N Zone Programming ✱ ✱ 56 and 58 Menu Modes) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ✱...
Page 44
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Each zone must be assigned to a zone type, which defines the way in Zone Type (ZT) 10 Zone Type which the system responds to faults in that zone. 00-24, 77, 90, 91 = zone type Perimeter Enter the Zone Type code from the list below: (see table at right)
Page 45
Zone Programming PROMPT VALID ENTRIES EXPLANATION Used only when enrolling wireless transmitters. Serial number Entry and 10 INPUT S/N: a. Transmit two open/close sequences. If using a button-type Loop Number Entry A 0 2 2 - 4 0 6 4 transmitter, press and release the button twice, but wait about 4 see explanation seconds before pressing the button the second time.
(zone number, zone type, loop number, etc.) relevant to that device. ∗ 58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming ADEMCO control panels. This mode is also used to program wireless keys using pre-defined templates.
Page 47
Zone Programming PROMPT VALID ENTRIES EXPLANATION Serial number Manually enter the serial number (found on the transmitter label), 10 INPUT S/N: by typing digits in the “X” locations, using the [A] (advance) or [B] S/N = serial number A X X X - X X X –...
Installation and Setup Guide Wireless Key Programming Templates This procedure programs the wireless keys, but a key is not active until it is assigned to a user number (see System Operation section, assigning attributes command). If the D key was previously pressed (from *58 Menu mode) to enter and duplicate 5804 and/or 5804BD wireless keys, the following screens appear.
Page 49
Zone Programming If the serial number transmitted does not match the serial number Not Confirmed Entd A022-4063 [ ∗ ] to continue entered, a display similar to the one shown will appear. If the loop Rcvd A022-4064 number does not match, it will also be displayed. If so, activate the button on the wireless key once again.
Installation and Setup Guide Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed: ∗79 Menu Mode PROMPT VALID ENTRIES EXPLANATION Device Output Number This is the logical (or reference) relay number as used in the system. ENTER OUTPUT NO.
Output Device Programming *80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types.
Page 54
Installation and Setup Guide Activated By Select where the initiating event for this output definition is to occur 01 Activated By: as follows: 0 = delete Zone List 0 = delete (deletes the output function and any previous 1 = zone list programming;-see prompt below) 2 = zone type 3 = zone number...
Page 55
Output Device Programming “C” Zone Number If zone number was selected, this screen appears. 01 Enter Zn No. Enter the desired zone number associated with this output number. Press [ ✱ ] to continue. Enter the zone event that will activate this output. 01 Enter Event 0 = restore;...
S E C T I O N Zone Lists (∗81) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Lists (*81 Menu Mode) Zone lists let you group individual zones for use with certain system actions.
Page 58
Installation and Setup Guide Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • When creating zone list 4 for cross zoning, include only zones assigned to zone types 3, 4, or 5. Do not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these zone types may produce unpredictable operation and may not function as intended.
S E C T I O N Function Key Programming (✱57 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Function Key Programming The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations.
S E C T I O N Alpha Descriptor Programming (*82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults.
Page 62
Installation and Setup Guide To delete or change the default descriptor for zone 1, press [ ✱ ] plus Flashing Cursor ✱ Z N 0 1 the same zone number (01). This will clear that descriptor and allow changes to be made at the flashing cursor. [∗] to continue NOTE: If you do not wish to change the existing descriptor for zone 1, enter [ ✱...
Alpha Descriptor Programming Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten characters can be used for each word or word string.
Page 64
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) (Word Space) LEVEL • 059 DOWN • 161 RIGHT • 219 WING • 109 LIBRARY ∗ • 162 ROOM ∗ WIRELESS • 060 DOWNSTAIRS – A – DRAWER – X – • 110 LIGHT ROOF •...
S E C T I O N Creating Schedules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The VISTA-20P system provides up to 32 schedules (VISTA-15P supports 8), which can be used to control 11 types of system events at pre-defined times.
Page 66
Installation and Setup Guide Enter the event’s start time and days of the week to occur. Start Time S T A R T S M T W T F S To select days, position the cursor under the desired days using the 01-12 = hour 0 0 1 0 0 0 0 H H M M A M...
3 (or 4) times and is followed by the second digit. This is the “expanded” digit. 4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. ADEMCO Contact ID Comprises a 4- or 10-digit subscriber number (depending on format Reporting Format selected), 1-digit event qualifier (“new” or “restore”), 3-digit event code, and 3-digit zone number, user number, or system status number (see the following page).
Duress = 92 3 + #, or C = 96 ® Ademco Contact ID ® The Ademco Contact ID Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected). 1-digit event qualifier (“new” or “restore”). 3-digit event code.
Page 69
System Communication ® Ademco Contact ID Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ where: CCCC(CCCCCC) = Customer (subscriber) ID Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office receiver manual.
S E C T I O N System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The VISTA-20P system supports up to 48 security codes (VISTA-15P supports 32 codes), which can each be assigned one of 5 authority levels.
Installation and Setup Guide Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For AUI users, refer to the separate AUI User’s Guide. Voice Keypads The 6150V/6160V Voice Keypads provide the following features: •...
System Operation Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
Installation and Setup Guide Various System Trouble Displays Alpha Display Fixed Disp. Meaning CANCELED ALARM will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time.
S E C T I O N Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:...
Installation and Setup Guide Checking Transmitter Enrollment (Sniffer Mode) Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command. 1. Press [Installer code] + [#] + 3. Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
Testing the System Dialer Communication Test and Periodic Test Reports 1. Enter Installer Code + 5 [ TEST ], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK (no special display on Fixed-Word keypads) The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd”...
1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Voltage: 13.8VDC.
Page 80
1321: 16.5VAC, 25VA Plug-In Transformer (No. 1321CN in Canada) Transformers: 1321X10: Powerline Carrier device Interface AC Transformer 4300: Powerline Carrier device Interface AC Transformer Ademco AB-12M 10” Motorized Bell & Box Sounders: Ademco 1011BE12M 10” Motorized Bell & Box Ademco 702 Outdoor Siren...
Specifications 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). NOTE: For information on any transmitter not LOOP 3 LOOP...
Page 82
Installation and Setup Guide Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description Has three unique input (loop) codes: one for a “Primary” contact 5817 Multi-Point Universal loop with programmable options; the others for two “auxiliary” Transmitter closed circuit contact loops. •...
S E C T I O N Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules.
Page 86
Installation and Setup Guide UL NOTICES ✱ ✱ 1. Entry Delay No. 1 and No. 2 (fields 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
S E C T I O N Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against...
Page 88
Installation and Setup Guide WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Page 96
24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
Need help?
Do you have a question about the VISTA-20PS Series and is the answer not in the manual?
Questions and answers